2023-03-03 10:19:56 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 23021392 |
| 3/3/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS ISO #1 & #2: PLEASE PROVIDE THE TOTAL LOW |
| PRESSURE PIPING RUN LENGTH FROM THE REGULATOR TO THE |
| RANGE- SEC. G2413.14.1 FBC RES. IT APPEARS THE RUN IS |
| GREATER THAN 20 FT. SO THE 1/2-INCH GALVANIZED AND |
| 3/4-IINCH CSST (25-EHD) ARE UNDERSIZED PER TABLES |
| G24134(1) [402.4(2)], AND G2413.4(5) [402.4(15) ]. |
| |
| 2) SURVEY: PLEASE PROVIDE A CLEARER APPLIANCE AND |
| PIPING LOCATION PLAN THAT CLEARLY SHOWS THE ACTUAL |
| PHYSICAL LOCATIONS OF THE NEW POOL HEATER, THE BBQ, THE |
| TANKLESS WATER HEATER AND THE DRYER- SEC. 107.2.1 WPB. |
| THE PLAN SHALL PROVIDE DETAILS AND NOTES IN COMPLIANCE |
| WITH THE FBC RES ITEMS A, B, C, ,& E LISTED BELOW. |
| A) PE PIPING SHALL NOT BE INSTALLED UNDER ANY PORTION |
| OF THE EXISTING BUILDINGS- SEC. G2415.17.1. |
| B) THE GAS BBQ SHALL BE INSTALLED WITH CLEARANCES TO |
| COMBUSTIBLES PER THE MANUFACTURER???S INSTALLATION |
| INSTRUCTIONS AND MAY REQUIRE AN EXHAUST HOOD AND DUCT |
| IF INSTALLED UNDER OVERHEAD COMBUSTIBLE CONSTRUCTION- |
| SEC. G2447.1. |
| C) THE TANKLESS WATER HEATER SHALL BE INSTALLED WITH |
| CLEARANCES PER THE MANUFACTURER AND THE EXHAUST SHALL |
| BE MINIMUM 4 FT. AWAY FROM OPENINGS INTO THE BUILDING |
| INCLUDING OPERABLE WINDOWS AND DOORS, AND SOFFIT VENTS- |
| SECS. G2447.2.2, G2427.8 & G2448.1. PLEASE NOTE THE |
| MOST STRINGENT CLEARANCES SHALL APPLY. |
| D) SHOW THE ROOM THE DRYER WILL BE LOCATED IN AND THE |
| ROOM DIMENSIONS. PROVIDE COMBUSTION AIR AND EXHAUST |
| VENTILATION FOR THE DRYER- SEE SECS. G2407.1, G2438.1 & |
| G2439.1. |
| E) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE |
| POOL HEATER HOWEVER THE CURRENT PLAN SHALL SHOW THE |
| UNIT WILL BE INSTALLED WITH CLEARANCES PER THE |
| MANUFACTURER AND THE EXHAUST SHALL BE MINIMUM 4 FT. |
| AWAY FROM OPENINGS INTO THE BUILDING INCLUDING OPERABLE |
| WINDOWS AND DOORS, AND SOFFIT VENTS- SECS. G2447.2.2, |
| G2427.8 & G2441.1. PLEASE NOTE THE MOST STRINGENT |
| CLEARANCES SHALL APPLY. |
| |
| 3) SURVEY: IT APPEARS THE TANKLESS WATER HEATER IS |
| BEING INSTALLED AT THE GARAGE. PLEASE CLARIFY IF THE |
| GARAGE IS BEING CONVERTED INTO LIVING SPACE AND INCLUDE |
| INSTALLATION OF NEW PLUMBING FIXTURES AND PIPING- SEC. |
| 107.2.1 WPB. |
| |
| 4) THE GAS RISER DRAWINGS AND LOCATION PLAN SHALL BEAR |
| THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR WHO |
| PREPARED THE DRAWING- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |