2023-03-21 17:17:25 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23021319 |
| 3/20/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS D1.1 & P1.1: SHOW THE SLAB CUT AREAS ON THE |
| D1.1 WHERE UNDERSLAB SANITARY PIPING IS BEING REMOVED |
| AS SHOWN ON P1.1- SEC. 107.2.1 WPB. |
| |
| 2) P1.1: IT APPEARS THE DRAIN LINE FOR THE MOP SINK IS |
| BEING REMOVED. IS THE DRAIN FOR THE SINK BEING |
| RELOCATED? PLEASE NOTE THAT A SERVICE SINK IS A |
| REQUIRED FIXTURE FOR AN A2 OCCUPANCY- TABLE 403.1 FBC |
| P. |
| |
| 3) P1.1: SHOW THE LOCATION OF THE WATER FILTRATION |
| SYSTEM ON THE PLUMBING FLOOR PLAN DRAWING, THE 3/4-INCH |
| WATER LINE CONNECTION POINT, AND THE BACKFLOW |
| PREVENTER- SEC. 107.2.1 WPB. |
| |
| A) PROVIDE THE TYPE OF BACKFLOW PREVENTER TO BE |
| INSTALLED- SEC. 608.3 FBC P. |
| |
| 4) P1.1: SHOW THE LOCATION OF THE NEW FLOOR SINK (FS IN |
| THE SCHEDULE)- SEC. P1.1 FBC P. |
| |
| 5) P1.1: IDENTIFY THE PLUMBING FIXTURE TO BE INSTALLED |
| AT 101B CONDIMENTS- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |