2023-03-21 17:17:251ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23021319
 3/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS D1.1 & P1.1: SHOW THE SLAB CUT AREAS ON THE
 D1.1 WHERE UNDERSLAB SANITARY PIPING IS BEING REMOVED
 AS SHOWN ON P1.1- SEC. 107.2.1 WPB.
  
 2) P1.1: IT APPEARS THE DRAIN LINE FOR THE MOP SINK IS
 BEING REMOVED. IS THE DRAIN FOR THE SINK BEING
 RELOCATED? PLEASE NOTE THAT A SERVICE SINK IS A
 REQUIRED FIXTURE FOR AN A2 OCCUPANCY- TABLE 403.1 FBC
 P.
  
 3) P1.1: SHOW THE LOCATION OF THE WATER FILTRATION
 SYSTEM ON THE PLUMBING FLOOR PLAN DRAWING, THE 3/4-INCH
 WATER LINE CONNECTION POINT, AND THE BACKFLOW
 PREVENTER- SEC. 107.2.1 WPB.
  
 A) PROVIDE THE TYPE OF BACKFLOW PREVENTER TO BE
 INSTALLED- SEC. 608.3 FBC P.
  
 4) P1.1: SHOW THE LOCATION OF THE NEW FLOOR SINK (FS IN
 THE SCHEDULE)- SEC. P1.1 FBC P.
  
 5) P1.1: IDENTIFY THE PLUMBING FIXTURE TO BE INSTALLED
 AT 101B CONDIMENTS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  