2023-03-29 13:50:22FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION, INCLUDE EXISTING AND NEW
 LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE.
 NEC 220
  
 2. PROVIDE INFORMATION OF THE ELECTRICAL PANEL (RATING
 AND PROTECTION) WHERE THESE LOADS ARE CONNECTED ALONG
 WITH THE PANEL SCHEDULE. NEC 240, 408.4(A)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  