2023-03-02 13:57:351ST REVIEW FMC
 PERMIT: 23021309
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED DRAWING DOES NOT SHOW THE RETURN AIR
 PATH FROM THE OFFICE TO THE FOYER AS PREVIOUSLY SHOWN
 ON THE ORIGINAL APPROVED PLAN. PROVIDE THE RETURN AIR
 PATH ON THE DRAWINGS. FM+RC M1602.3
  
 2) SHOW THE CONDENSING UNITS LOCATION ON THE REVISED
 DRAWING. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  