2023-04-03 15:11:20 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-23021308 |
| 4/3/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P1.1 & P3.1: THE URINAL FIXTURE DRAIN CANNOT |
| CONNECT TO THE 3-INCH HORIZONTAL WET VENT FOR THE |
| BATHROOM FIXTURES- SEC. 202 & 912.1 FBC P. RELOCATE THE |
| DRAIN CONNECTION EITHER UPSTREAM OR DOWNSTREAM OF THE |
| WET VENT. |
| |
| 2) P2.1 & P3.1: THE THERMOSTAT CONTROL ON THE WATER |
| HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER |
| DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE |
| FOR THE PURPOSE OF HOT WATER DELIVERY. THIS CAN BE |
| ACCOMPLISHED BY INSTALLING A MASTER THERMOSTATIC MIXING |
| VALVE AT THE WATER HEATER. THIS WOULD BE IN ADDITION TO |
| THE REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC |
| HAND-WASHING- SEC. 607.1.1 FBC P. |
| |
| 3) P2.1 & P3.1: PROVIDE A THERMAL EXPANSION CONTROL |
| DEVICE AT THE WATER HEATER- SEC. 607.3 FBC P. |
| |
| 4) P3.1: PROVIDE A PLUMBING FIXTURE SCHEDULE AND A |
| EQUIPMENT SCHEDULE FOR THE WATER HEATER- SEC. 404.1 & |
| 502.1 FBC P. |
| |
| 5) A4.01: PROVIDE THE FOLLOWING DETAILS IN COMPLIANCE |
| WITH THE FBC ACC. |
| |
| A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| SEC. 604.3. |
| |
| B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| SEC. 606.2. |
| |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| |
| D) CENTERLINES OF THE ACCESSIBLE WATER CLOSETS FROM THE |
| SIDE WALLS- SEC. 604.2. |
| |
| E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- SEC. 604.4. |
| |
| F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| |
| G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SEC. 603.3 |
| |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| FIGURES 604.5.1 & 604.5.2. |
| |
| I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| FIGURE 604.7. |
| |
| J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| 606.2 |
| |
| K) CLEAR FLOOR SPACE DIMENSIONS FOR THE WHEELCHAIR |
| ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2. |
| |
| L) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR |
| ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2. |
| |
| M) SPOUT HEIGHTS- SECS. 602.4 & 602.7. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |