Plan Review Notes For Permit 23021305 |
Permit Number |
23021305 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-06-22 17:58:36 | BUILDING REVIEW APPROVED WITH PROVISO (PER ARCHITECT'S | | REQUEST): | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | | 1- CHANGE OF OCCUPANCY FROM R2 TO R3. CERTIFICATE OF | | OCCUPANCY REQUIRED. SEC. 1001.3 FBC-EXISTING BUILDING. | | | | 2- PROVIDE PRODUCT APPROVAL FOR: | | A)CABANA BIFOLD DOOR AS SHOWN ON PLANS. | | B)HURRICANE SHUTTERS IF ABOVE DOORS DON'T HAVE IMPACT | | GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. | | SEE CITY SAMPLE. | | C)RESUBMIT SINGLE HUNG WINDOWS AND FRENCH DOORS PRODUCT | | APPROVALS. THEY WERE REVISED AND WERE NOT APPROVED BY | | THE ARCHITECT. | | |
|