2023-03-10 12:08:48 | 1ST REVIEW FMC |
| PERMIT: 23010083 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COULD NOT COMPLETE A MECHANICAL REVIEW AS NOT ALL OF |
| THE INFORMATION WAS PROVIDED. |
| |
| 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| INDICATES 4 ZONES. LABEL THESE ZONES ON THE MECHANICAL |
| DRAWINGS. FBC 107.3.5 |
| |
| 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| INDICATES THAT ZONE 4 DOES NOT HAVE A HEATING INPUT OR |
| OUTPUT. PLEASE EXPLAIN HOW THIS WOULD MEET THE HEATING |
| REQUIREMENTS OF FRC R303.10 |
| |
| 3) PROVIDE AN EQUIPMENT SCHEDULE SHEET FOR ALL OF THE |
| MECHANICAL SYSTEMS INCLUDING THE BATH EXHAUST FANS. FBC |
| 107.3.5 |
| |
| 4) PROVIDE INFORMATION FOR THE KITCHEN HOOD MOTOR. WHAT |
| ARE THE CFMS? IF NEEDED SHOW THE MAKEUP AIR FOR THIS |
| FAN. FRC M1503.4 |
| |
| 5) SHOW HOW THE 6 INCH DRYER EXHAUST DUCT SIZE WILL |
| MEET FRC M1502.4.1 |
| |
| 6) PROVIDE THE MECHANICAL DESIGN FOR THE ACCESSORY |
| STRUCTURE. FBC 1073.5 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |