2023-03-22 19:05:34 | BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23021305 |
| 230 ARGYLE RD (GARAGE/APT. ALTERATION) |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. |
| 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. |
| ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- SOUTH BUILDING SCOPE OF WORK IS NOT CLEAR: |
| A)ACCORDING TO CITY RECORDS, THE SOUTH BUILDING HAS A |
| GARAGE AND ONE APARTMENT ON THE FIRST FLOOR AND TWO |
| APARTMENTS ON THE SECOND FLOOR (THREE UNITS TOTAL). |
| SCOPE OF WORK SHOWN ON PLANS IS NOT CLEAR. IT LOOKS |
| LIKE THE UNIT ON THE FIRST FLOOR IS GOING TO BE |
| CONVERTED TO A POOL CABANA AND THE SECOND FLOOR IS |
| GOING TO BE CONVERTED TO A SINGLE APARTMENT. REVISE |
| SCOPE OF WORK ON PERMIT APPLICATION AND PLANS |
| DESCRIPTION TO CLEARLY INDICATE EXISTING AND PROPOSED |
| USE. A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 1001 FBC-EXISTING |
| BUILDING. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B)DEMOLITION PLAN ON SHEET 6 HAS NOTE STATING "NO WORK |
| @ SECOND FLOOR OF ACCESSORY STRUCTURE". THE SECOND |
| FLOOR PLAN OF THE SOUTH BUILDING SHOWS A SINGLE |
| DWELLING UNIT WITH 2 KITCHENS. ACCORDING TO CITY |
| RECORDS, . THE SOUTH BUILDING HAS TWO APARTMENTS ON THE |
| SECOND FLOOR. THERE ARE NO PERMITS ON RECORD FOR THE |
| UNIFICATION OF THE TWO DWELLING UNITS INTO ONE. PROVIDE |
| COMPLETE INFORMATION ON PLANS SHOWING THE CONVERSION. |
| REVISE SCOPE OF WORK ON PERMIT APPLICATION AND PLANS TO |
| CLEARLY INDICATE EXISTING AND PROPOSED USE. A NEW |
| CERTIFICATE OF OCCUPANCY WILL BE REQUIRED. SEC. 606 |
| FBC-EXISTING BUILDING. SEC. 1001 FBC-EXISTING BUILDING. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- PROJECT LOCATION SHOWN ON SHEET 2 IS INCORRECT. |
| REVISE MAP VIEW AND AERIAL VIEW. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: ARCHITECT TO SHOW NORTH ARROW ON EACH FLOOR PLAN |
| TO AVOID CONFLICTS/DELAYS. |
| |
| 3- ENERGY CALCULATIONS: |
| A)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH |
| BUILDING. MAIN HOUSE AND GARAGE/APT STRUCTURE. SEC. |
| R101.3 FBC-ENERGY CONSERVATION. |
| NOTE: ENERGY CALCULATIONS WILL BE REVIEWED ONCE THEY |
| ARE SUBMITTED FOR EACH BUILDING TO VERIFY BUILDING |
| SPECIFIC INFORMATION. |
| |
| B)SUBMIT ENERGY CALCULATIONS AND A/C EQUIPMENT LOAD |
| CALCULATIONS ON SEPARATE PDF FILES. THIS WILL HELP |
| EXPEDITE THE REVIEW PROCESS AND WILL HELP TO AVOID |
| CONFLICTS/DELAYS IF ENERGY CALCULATIONS ARE APPROVED |
| AND EQUIPMENT SIZING CALCULATIONS ARE NOT OR VICE VERSA |
| SINCE A/C CALCULATIONS ARE DONE UNDER A SEPARATE |
| MECHANICAL REVIEW. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| JURISDICTION NUMBER (THIS JURISDICTION IS 604700). |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D)ROOF TYPE AND MATERIAL TO MATCH PLANS FOR EACH |
| BUILDING. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) REVISE DOORS INFORMATION. IT LOOKS LIKE THE |
| INFORMATION SUBMITTED IS FOR THE OVERHEAD GARAGE DOOR. |
| DOORS INFORMATION IS FOR THE DOORS SEPARATING A/C AREAS |
| FROM NON-A/C AREAS. NOT FROM GARAGE TO OUTSIDE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE WINDOWS INFORMATION TO MATCH PLANS. REVISE |
| WINDOWS ORIENTATION, AREA AND OVERHANG DEPTH AND |
| SEPARATION TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 4- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR |
| LATER AS A DEFERRED SUBMITTAL). |
| |
| A)ENTRY DOOR NOA 21-0510.09 SUBMITTED DOESN'T MEET THE |
| CALCULATED DESIGN PRESSURES SHOWN ON SHEET 2. NEED DOOR |
| THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| SEC R301.2.1 FBC-RESIDENTIAL. |
| |
| B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| FOR ALL HORIZONTAL AND VERTICAL MULLIONS TO BE |
| INSTALLED TO VERIFY PRESSURES. SEC. R301.2.1 |
| FBC-RESIDENTIAL). |
| |
| C)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS. INFORMATION |
| SUBMITTED IS NOT A PRODUCT APPROVAL. |
| |
| D) GARAGE FRENCH DOORS AS SHOWN ON PLANS. |
| |
| 5-DESIGNER OF RECORD TO REVIEW PRODUCT APPROVALS THAT |
| ARE NEW OR REVISED. SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| ********************************** |
| |
| |
| |
| |
| |
| |