Plan Review Notes For Permit 23021165
Permit Number 23021165
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-24 10:30:35JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 908.2 PROVIDE CERTIFICATION THAT THE EXISTING
 STRUCTURAL ROOF COMPONENTS CAN SUPPORT THE NEW CONCRETE
 ROOFING TILE SYSTEM TO BE USED.
 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED SKYLIGHT SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL14317-R13
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECT
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1
 DIRECT-TO-DECK PAGES #4 OR #5. SYSTEM SELECTED MUST
 MEET OR EXCEED -124 MAXIMUM DESIGN PRESSURE. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 4. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS
 TO INDICATE REROOFING LOW/FLAT SLOPE AREA; IF NOT
 INDICATE BY PLACING AN X IN LOW/FLAT SLOPE AREAS; IF TO
 RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF 2020 CODE
 VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT
 ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. REVISE
 ROOF DIAGRAM/SKETCH TO INCLUDE MEAN ROOF HEIGHT(S).
 5. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  