Plan Review Notes For Permit 23021112 |
Permit Number |
23021112 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-05-26 08:49:55 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 23021112 | | 5/25/2023 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE TWO NEW FLOOR PLANS 001 & 002 DO NOT MATCH. ONE | | DRAWING SHOWS THE KITCHENS AND BATHS AT THE FRONT SIDE | | OF THE AND THE OTHER SHOWS THE KITCHENS AND BATHS AT | | THE REAR. PLEASE CHOOSE ONE PLAN OR THE OTHER AND | | PROVIDE A WRITTEN SCOPE OF WORK FOR PLUMBING ON THE | | PLAN WITH CORRESPONDING DETAILS. PROVIDE A SEPARATE | | PLUMBING PLAN IF NECESSARY. THE PREVIOUS RESPONSE TO | | COMMENTS INDICATED WATER HEATER REPLACEMENTS ONLY. IF | | THAT IS THE ENTIRE SCOPE THEN INDICATE THAT ON THE | | PLANS AND PROVIDE EQUIPMENT SCHEDULES FOR EACH WATER | | HEATER INDICATING THE MAKES AND MODELS AND GALLON | | CAPACITIES- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|