2023-03-09 07:26:131ST REVIEW FMC
 PERMIT: 23021085
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT.
 FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC R403.7.1
  
 3) THE RETURN FOR AHU-3 CANNOT BE FROM THE CLOSET. FRC
 M1602.2 ITEM 4.
  
 4) PROVIDE THE RETURN AIR PATH FOR THE NEW BEDROOM. FRC
 M1602.3
  
 5) SHEET M-1 INDICATES AN EF-2 100 CFM, SHOW THIS FAN
 IN THE EXHAUST FAN SCHEDULE ON SHEET M-2. FBC 107.3.5
  
 6) THE DESIGNER OF THE MECHANICAL DRAWINGS MUST
 DIGITALLY SIGN EACH SHEET. FS 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  