Plan Review Notes For Permit 23021085 |
Permit Number |
23021085 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-16 12:02:48 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) GENERATOR REQUIRES SEPARATE PLANS AND PERMIT. | | | | 2) ALL 120 VOLT 15 AND 20 AMP RECEPTACLE OUTLETS IN | | LAUNDRY ROOM TO BE GFCI PROTECTED. 210.8(A)(10) | | | | 3) OUTLET SPACING ON WORK SURFACE COUNTER IN LAUNDRY | | AREA MAY NEED ADDITIONAL OUTLETS. 210.52(C)(1) |
|