Plan Review Notes
Plan Review Notes For Permit 23021078
Permit Number 23021078
Review Stop B
Sequence Number 2
Notes
Date Text
2023-03-10 15:34:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 COURTESY REVIEW VIA EMAIL
  
 1. FBC R 703.4, FBC B 1405.4, PRODUCT SHEET FOR DOWSILL
 CONTRACTOR'S PAINTABLE SEALANT WAS SUBMITTED VIA EMAIL.
 THIS PRODUCT APPEARS TO COMPLY WITH ASTM C-920 FOR
 CAULKING. IT IS NOT CLEAR WITH WHICH METHOD IN FBC R
 703.4 THIS COMPLIES FOR FLASHING, SEE OPTIONS BELOW.
 SENT OPTIONS TO CONTRACTOR VIA EMAIL.
  
 R703.4FLASHING.
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS. METAL FLASHING SHALL
 BE CORROSION RESISTANT. FLUID-APPLIED MEMBRANES USED AS
 FLASHING SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS. ALL FLASHING SHALL BE
 APPLIED IN A MANNER TO PREVENT THE ENTRY OF WATER INTO
 THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING
 STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED MEMBRANES
 USED AS FLASHING SHALL COMPLY WITH AAMA 711. ALL
 EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT THE
 JUNCTURE WITH THE BUILDING WALL WITH A SEALANT
 COMPLYING WITH AAMA 800 OR ASTM C920 CLASS 25 GRADE NS
 OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION,
 ASTM C1281, AAMA 812, OR OTHER APPROVED STANDARD AS
 APPROPRIATE FOR THE TYPE OF SEALANT. FLUID-APPLIED
 MEMBRANES USED AS FLASHING IN EXTERIOR WALLS SHALL
 COMPLY WITH AAMA 714. THE FLASHING SHALL EXTEND TO THE
 SURFACE OF THE EXTERIOR WALL FINISH. APPROVED FLASHINGS
 SHALL BE INSTALLED AT THE FOLLOWING LOCATIONS:
  
 1.EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT
 EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND TO THE
 SURFACE OF THE EXTERIOR WALL FINISH OR TO THE
 WATER-RESISTIVE BARRIER COMPLYING WITH SECTION 703.2
 FOR SUBSEQUENT DRAINAGE. MECHANICALLY ATTACHED FLEXIBLE
 FLASHINGS SHALL COMPLY WITH AAMA 712. FLASHING AT
 EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN
 ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING:
  
 1.1.THE FENESTRATION MANUFACTURER???S INSTALLATION AND
 FLASHING INSTRUCTIONS, OR FOR APPLICATIONS NOT
 ADDRESSED IN THE FENESTRATION MANUFACTURER???S
 INSTRUCTIONS, IN ACCORDANCE WITH THE FLASHING
 MANUFACTURER???S INSTRUCTIONS. WHERE FLASHING
 INSTRUCTIONS OR DETAILS ARE NOT PROVIDED, PAN FLASHING
 SHALL BE INSTALLED AT THE SILL OF EXTERIOR WINDOW AND
 DOOR OPENINGS. PAN FLASHING SHALL BE SEALED OR SLOPED
 IN SUCH A MANNER AS TO DIRECT WATER TO THE SURFACE OF
 THE EXTERIOR WALL FINISH OR TO THE WATER-RESISTIVE
 BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN
 FLASHING SHALL INCORPORATE FLASHING OR PROTECTION AT
 THE HEAD AND SIDES.
  
 1.2.IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF
 A REGISTERED DESIGN PROFESSIONAL.
  
 1.3.IN ACCORDANCE WITH OTHER APPROVED METHODS.
  
 1.4IN ACCORDANCE WITH FMA/AAMA 100, FMA/AAMA 200,
 FMA/WDMA 250, FMA/AAMA/WDMA 300 OR FMA/AAMA/WDMA 400.
  
 2. FS471, THE ENGINEERING IS NOT DIGITALLY SIGNED.
 EITHER UPLOAD DIGITALLY SIGNED ENGINEERING OR EMAIL
 [email protected] AND REQUEST THAT IT BE DELETED.
  
  