2023-03-10 15:34:22 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC R = FBC RESIDENTIAL |
| |
| COURTESY REVIEW VIA EMAIL |
| |
| 1. FBC R 703.4, FBC B 1405.4, PRODUCT SHEET FOR DOWSILL |
| CONTRACTOR'S PAINTABLE SEALANT WAS SUBMITTED VIA EMAIL. |
| THIS PRODUCT APPEARS TO COMPLY WITH ASTM C-920 FOR |
| CAULKING. IT IS NOT CLEAR WITH WHICH METHOD IN FBC R |
| 703.4 THIS COMPLIES FOR FLASHING, SEE OPTIONS BELOW. |
| SENT OPTIONS TO CONTRACTOR VIA EMAIL. |
| |
| R703.4FLASHING. |
| APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED |
| MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING |
| SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH |
| THE MANUFACTURER???S INSTRUCTIONS. METAL FLASHING SHALL |
| BE CORROSION RESISTANT. FLUID-APPLIED MEMBRANES USED AS |
| FLASHING SHALL BE APPLIED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTRUCTIONS. ALL FLASHING SHALL BE |
| APPLIED IN A MANNER TO PREVENT THE ENTRY OF WATER INTO |
| THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING |
| STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED MEMBRANES |
| USED AS FLASHING SHALL COMPLY WITH AAMA 711. ALL |
| EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT THE |
| JUNCTURE WITH THE BUILDING WALL WITH A SEALANT |
| COMPLYING WITH AAMA 800 OR ASTM C920 CLASS 25 GRADE NS |
| OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, |
| ASTM C1281, AAMA 812, OR OTHER APPROVED STANDARD AS |
| APPROPRIATE FOR THE TYPE OF SEALANT. FLUID-APPLIED |
| MEMBRANES USED AS FLASHING IN EXTERIOR WALLS SHALL |
| COMPLY WITH AAMA 714. THE FLASHING SHALL EXTEND TO THE |
| SURFACE OF THE EXTERIOR WALL FINISH. APPROVED FLASHINGS |
| SHALL BE INSTALLED AT THE FOLLOWING LOCATIONS: |
| |
| 1.EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT |
| EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND TO THE |
| SURFACE OF THE EXTERIOR WALL FINISH OR TO THE |
| WATER-RESISTIVE BARRIER COMPLYING WITH SECTION 703.2 |
| FOR SUBSEQUENT DRAINAGE. MECHANICALLY ATTACHED FLEXIBLE |
| FLASHINGS SHALL COMPLY WITH AAMA 712. FLASHING AT |
| EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN |
| ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING: |
| |
| 1.1.THE FENESTRATION MANUFACTURER???S INSTALLATION AND |
| FLASHING INSTRUCTIONS, OR FOR APPLICATIONS NOT |
| ADDRESSED IN THE FENESTRATION MANUFACTURER???S |
| INSTRUCTIONS, IN ACCORDANCE WITH THE FLASHING |
| MANUFACTURER???S INSTRUCTIONS. WHERE FLASHING |
| INSTRUCTIONS OR DETAILS ARE NOT PROVIDED, PAN FLASHING |
| SHALL BE INSTALLED AT THE SILL OF EXTERIOR WINDOW AND |
| DOOR OPENINGS. PAN FLASHING SHALL BE SEALED OR SLOPED |
| IN SUCH A MANNER AS TO DIRECT WATER TO THE SURFACE OF |
| THE EXTERIOR WALL FINISH OR TO THE WATER-RESISTIVE |
| BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN |
| FLASHING SHALL INCORPORATE FLASHING OR PROTECTION AT |
| THE HEAD AND SIDES. |
| |
| 1.2.IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF |
| A REGISTERED DESIGN PROFESSIONAL. |
| |
| 1.3.IN ACCORDANCE WITH OTHER APPROVED METHODS. |
| |
| 1.4IN ACCORDANCE WITH FMA/AAMA 100, FMA/AAMA 200, |
| FMA/WDMA 250, FMA/AAMA/WDMA 300 OR FMA/AAMA/WDMA 400. |
| |
| 2. FS471, THE ENGINEERING IS NOT DIGITALLY SIGNED. |
| EITHER UPLOAD DIGITALLY SIGNED ENGINEERING OR EMAIL |
| [email protected] AND REQUEST THAT IT BE DELETED. |
| |
| |