Plan Review Notes
Plan Review Notes For Permit 23021053
Permit Number 23021053
Review Stop P
Sequence Number 2
Notes
Date Text
2023-05-01 07:09:302ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021053
 5/1/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW PRINTED BELOW STILL EXISTS. PLEASE PROVIDE A
 DIGITALLY SIGNED AND SEALED P-1 PLAN SHEET WITH A
 SIGNATURE AND SEAL CAPABLE OF BEING VERIFIED.
  
 1) SHEET P1: THE DIGITAL SIGNATURE AND SEAL OF THE
 ENGINEER ON THE PLUMBING PLAN SHEET CANNOT BE VERIFIED
 DUE TO AN UPLOADING OR TRANSMITTAL ERROR WHICH
 TERMINATES THE PROCESS. THE ERROR MESSAGE INDICATES
 INCORRECT, UNRECOGNIZED OR SUSPICIOUS DATA- SEE FL.
 STATUTE 471.025 AND FAC SEC. G61G15-23.005.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  