2023-03-25 09:58:11 | 1ST BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| SURVEY. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE A SITE PLAN.... |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE |
| AND INCLUDED BOUNDARY LINE SURVEY. |
| |
| 3. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| 4. PROVIDE A COMPLETE RESIDENTIAL ENERGY SUBMITTAL (RE) |
| R401.2COMPLIANCE. |
| SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| THROUGH R404 LABELED MANDATORY. |
| |
| 5.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. |
| R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO |
| ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES |
| (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 |
| SQUARE FEET (2.8 M2). |
| |
| 6.PROVIDE SMOKE ALARMS. |
| FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| BUILDING. |
| |
| SMOKE ALARMS |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |