Date |
Text |
2023-03-13 09:10:45 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| 21-1229.01 SYSTEM TYPE C (1) MAXIMUM DESIGN PRESSURE |
| -52.5 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN |
| PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C |
| AREAS. GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED |
| TO IN THIS NOA. THE MAXIMUM DESIGNED PRESSURE |
| LIMITATION LISTED SHALL BE APPLICABLE TO ALL ROOF |
| PRESSURE ZONES (I.E. FIELD, PERIMETERS, AND CORNERS). |
| NEITHER RATIONAL ANALYSIS, NOR EXTRAPOLATION SHALL BE |
| PERMITTED FOR ENHANCED FASTENING AT ENHANCED PRESSURE |
| ZONES (I.E. PERIMETERS, EXTENDED CORNERS AND CORNERS). |
| THIS SYSTEM CAN???T BE USED. PROVIDE SYSTEM THAT MEETS |
| OR EXCEEDS THESE REQUIREMENTS. |
| 2. FBC EB 706.8.1 PROVIDE A DETAILED COST ESTIMATE OF |
| THE EVALUATION AND INSTALLATION OF CONNECTIONS AT THE |
| GABLE ENDS OR ALL CORNERS THAT WILL EXCEED 15% OF THE |
| COST OF THE ROOF REPLACEMENT WHEN COMPLETED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |