2023-02-21 11:11:00 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| |
| 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL7849-R17 HAS NOT BEEN APPROVED YET. PLEASE |
| PROVIDE A COMPLETE SET OF APPROVED 2020 CODE VERSION |
| PRODUCT APPROVALS/NOA???S FOR THE PROPOSED CONCRETE |
| ROOF TILE SYSTEM USED. INCLUDE COVER PAGE, EVALUATION |
| REPORTS PAGES 1-7. (FL7849-R16) |
| 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL11727-R15 HAS BEEN REVISED TO FL11727-R16. |
| PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. PLEASE VERIFY THE SELECTED |
| SYSTEM USED WILL MEET OR EXCEEDS THE MINIMUM DESIGN |
| PRESSURE REQUIREMENTS AS PER THE SIGN AND SEALED |
| ENGINEERED DESIGN PRESSURE CALCULATIONS; ALSO VERIFY |
| THE SELECTED UNDERLAYMENT SYSTEM WILL ALSO MEET THAT |
| REQUIREMENT. |
| 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL14207-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY. |
| 4. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA |
| 18-0717.05 COVERS MULTIPLE PRODUCTS & MAXIMUM DESIGN |
| PRESSURE APPLICATION FROM TABLE 2 NEW CONSTRUCTION |
| PAGES 7-10. SELECT APPLICATION TO BE USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| 5. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. (FL5374-R6) |
| 6. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| 7. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED ENGINEERED TILE ROOF COVERING ATTACHMENT |
| CALCULATIONS BY A FLORIDA REGISTERED PROFESSIONAL |
| ENGINEER, REGISTERED ARCHITECT, OR REGISTERED ROOF |
| CONSULTANT. |
| 8. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| SUBMITTING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |