2023-07-06 17:11:37RESIDENTIAL(R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020716
 2735 EMBASSY DR.
  
 PROVISO NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR
 PRODUCT APPROVALS/ DEFERRED SUBMITTAL).
  
 ***IMPORTANT***
 BUILDING REVIEW WILL BE APPROVED WITH PROVISO ONCE THE
 ENERGY CALCULATIONS ARE CERTIFIED AT THE BOTTOM OF FORM
 BY THE OWNER OR AUTHORIZED AGENT AND THE ENGINEER
 ADDRESSES THE DIGITAL SIGNATURE REVIEW COMMENTS.
  
 ***IMPORTANT
 ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED
 AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
  
 1- LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT
 DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE IS KEPT WITHIN THE LOT AND NOT DIVERTED TO
 ADJACENT PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH THE FOLLOWING SECTIONS: R401.3
 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC.
 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 1- SITE DRAINAGE PLANS HAVE AN ENGINEER'S
 SELF-CERTIFIED DIGITAL SIGNATURE. ENGINEER CANNOT
 SELF-CERTIFY THE DIGITAL SIGNATURE. THIRD PARTY
 CERTIFICATION IS REQUIRED BY FAC 61G15-23.004. (NOTE:
 ENGINEER TO CONTACT THE BOARD OF ENGINEER'S FOR
 SELF-CERTIFIED DIGITAL SIGNATURE QUESTIONS).
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION: DIMENSIONS, RISERS, TREADS,
 NOSING, HANDRAILS, GUARDRAILS, ETC. SHOWING COMPLIANCE
 WITH SEC. R311.7 FBC-RESIDENTIAL.
  
 RESPONSE:
 EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE
 DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE DESIGN
 GUIDELINES REQUIRED BY TABLE R301.5, SEC. R311.7. AND
 SEC. R312.1 FBC-RESIDENTIAL. NOTE: JUST CITING THE CODE
 SECTION IS NOT ALLOWED (SEC. 107.2.1 CITY AMENDMENTS).
 CLEARLY SPECIFY ON PLANS THE DESIGN GUIDELINES AND
 STATE ON DRAWINGS THAT SHOP DRAWINGS NEED TO BE
 SUBMITTED FOR DESIGNER OF RECORD REVIEW. ALL SHOP
 DRAWINGS TO BE REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
 NOTE: OPEN RISERS NEED TO MEET THE REQUIREMENTS OF SEC.
 R311.7.5.1 FBC-RESIDENTIAL.
  
 5- LIVING AREA SLIDING GLASS DOORS. BASED ON PLANS AND
 DOOR SCHEDULE, IT LOOKS LIKE THERE ARE TWO SLIDING
 GLASS DOORS MULLED TOGETHER. SPECIFY MULLION SIZE AND
 CONNECTIONS AND PROVIDE PRODUCT APPROVAL.. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE
 DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE MULLION
 TYPE, SIZE AND CONNECTORS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 8- BALCONY GUARDRAIL: IT IS NOT CLEAR WHAT TYPE OF
 RAILING IS GOING TO BE INSTALLED. SECOND FLOOR PLANS
 SPECIFIES 36" HIGH RAILING W/ PICKETS TO REJECT A 4"
 DIAM. SPHERE, WHILE REAR ELEVATION SHOWS GUARDRAIL THAT
 LOOKS LIKE A CABLE SYSTEM. REVISE AS REQUIRED TO MATCH
 AND PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 RESPONSE:
 EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE
 DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE DESIGN
 GUIDELINES REQUIRED BY TABLE R301.5, SEC. R311.7. AND
 SEC. R312.1 FBC-RESIDENTIAL.
  
 11-PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS CONSTRUCTION AND INSTALLATION. SPECIFY
 FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 WILL BE A DEFERRED SUBMITTAL.
  
 18- PRODUCT APPROVALS DEFERRED SUBMITTAL AFTER PERMIT
 IS ISSUED(APPROVED BY ENGINEER OF RECORD):
 A)ALL EXTERIOR DOORS.
 B)ALL WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING.
 E)METAL ROOF (IF USED).
 F)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 H)ROOF TILE ADHESIVE(IF USED)LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 I)HIP & RIDGE METAL SUPPORT TO BE USED.
 J)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE
 TILE.
 K) FLAT ROOF. AND, CLEARLY MARK ASSEMBLY TO BE
 INSTALLED.
  
 20- ENERGY CALCULATIONS:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME (IF AVAILABLE),
 CORRECT PERMIT OFFICE (CITY OF WEST PALM BEACH NOT PALM
 BEACH COUNTY), JURISDICTION NUMBER (THIS JURISDICTION
 IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 OWNER'S NAME IS INCORRECT, BUILDER'S NAME IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED. PROVIDE NAME , NOT SIGNATURE.
  
 G)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY