2023-02-27 11:59:481ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23020716
 2/27/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-5 PLUMBING RISER: PLEASE INCREASE THE SIZE
 OF THE BUILDING DRAIN FROM 3-INCH TO 4-INCH AT THE
 POINT WHERE THE 3-INCH BRANCH FROM THE MASTER BATH AND
 BATHS 2 & 3 CONNECTS- TABLES P3004.1 & TABLE P3005.4.2
 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  