2023-04-24 15:43:05 | RESIDENTIAL(R2) THIRD BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23020661 |
| 1006 10TH ST |
| |
| 1- FLOORING SOUND INSULATION MATERIAL: |
| |
| ORIGINAL COMMENT: |
| (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| (2020). |
| |
| RESPONSE: |
| INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| USED. |
| |
| ORIGINAL COMMENT: |
| (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| |
| RESPONSE: |
| INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| USED. |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| FLOOR FINISH. |
| |
| |
| ORIGINAL COMMENT: |
| (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| |
| RESPONSE: |
| INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| USED. |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| FLOOR FINISH. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |