Plan Review Notes
Plan Review Notes For Permit 23020641
Permit Number 23020641
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-21 10:20:26ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE ALL DETAILS ON SUBPANEL WIRING, I.E.
 EQUIPMENT, OVERCURRENT PROTECTION, AND FEEDER
 CONDUCTORS SIZES. INCLUDE LOCATION OF OCP AND A PANEL
 SCHEDULE. NEC 215.5
  
 2) PLEASE PROVEDE INDICATIONS OF COMPLIANCE WITH NEC
 310.15 (B)(7)(2) FOR A SERVICE RATED 100 THROUGH 400
 AMPERES, THE SERVICE CONDUCTORS SUPPLYING THE ENTIRE
 LOAD ASSOCIATED WITH A ONE FAMILY DWELLING, OR THE
 SERVICE CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH AN INDIVIDUAL DWELLING UNIT IN
 A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT
 OF THE SERVICE RATING. PLEASE NOTICE, REDUCTION IN
 AMPACITY IS ONLY PERMITTED IF FEEDER CONDUCTORS SUPPLY
 THE ENTITE LOAD.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  