Plan Review Notes For Permit 23020616 |
Permit Number |
23020616 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-17 16:46:16 | | | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 23020616 | | 2/17/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS A1 & A2: THE PLANS SHOW DEMOLITION AND | | RELOCATION OF PLUMBING FIXTURES IN THE MASTER BATH | | WHICH WILL REQUIRE RELOCATION OR EXTENSIONS OF DRAIN | | AND VENT PIPING. PLEASE PROVIDE A SANITARY ISOMETRIC | | DRAWING- SEC. 107.3.5.1.3 WPB MINIMUM PLAN REVIEW | | CRITERIA. | | | | 2) PLEASE NOTE: NEW DRAIN PIPE PENETRATIONS OF THE | | EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE | | ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED | | AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN, | | OR NOTE THAT THE DETAIL WILL BE DEFERRED AND BE ONSITE | | AT TIME OF INSPECTION- SEC. 315.1 FBC P AND SEC. | | 107.3.4.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|