2023-02-28 09:29:49 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL1654-R31 HAS NOT BEEN |
| APPROVED YET; FL1654-R30 IS THE CURRENT APPROVED |
| VERSION. PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER |
| PAGE, EVALUATION REPORT PAGES 1-5 AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR PRODUCT |
| APPROVAL FL1654-R31 SYSTEM NO. W-194 DO NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| AS PER RULE 61G20-3. |
| 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL34539 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL |
| INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS |
| WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER, |
| STATUS, GENERAL INFORMATION ABOUT THE PRODUCT). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |