2023-02-23 15:36:161ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23020582
 2/23/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-2.0A REVISION 6: IT APPEARS THAT REVISION 4
 HAS BEEN LEFT OUT OF THE UPDATED PLAN SHEET. THE
 REVISION 4 PLAN SHEET SHOWED THE GREASE INTERCEPTORS
 RELOCATED FROM THE NORTH TO THE SOUTH SIDE OF THE
 BUILDING, AND ALSO SHOWED THE WATER HEATER DRAIN LINE
 RELOCATED TO THE NORTH EXTERIOR. PLEASE PROVIDE AN
 UP-TO-DATE SHEET THAT INCLUDES ALL THE REVISIONS, AND A
 REVISED NARRATIVE WHICH ITEMIZES THE CHANGES.
 A) THE REVISED PLAN SHEET SHOWS THE EASTSIDE STORM
 DRAIN LINE EXTERIOR DISCHARGE HAS BEEN RELOCATED FROM
 THE SOUTH TO THE NORTH SIDE. PLEASE SUBMIT A REVISED
 STORM DRAIN RISER DRAWING- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  