Date |
Text |
2023-03-13 11:58:52 | NEW COMMERCIAL BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) BUILDING RISK CATEGORY IS SHOWN AS II - AN ASSEMBLY |
| CLASSIFICATION WITH OVER 300 OCCUPANT LOAD WILL NEED TO |
| SHOW A RISK CATEGORY OF III WITH DESIGN WIND SPEEDS OF |
| 180MPH - FBC 1604.5 |
| |
| 2) PLEASE SHOW ON THE SITE PLAN THE STORM WATER FLOW |
| AWAY FROM THE BUILDING AND AWAY FROM ADJACENT PROPERTY |
| OR PROVIDE A STORM WATER PLAN - FBC WPB 107.2.5 SITE |
| PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
| |
| 3) EXTERIOR DOOR (110B) NEEDS TO BE 3/4 HOUR FIRE RATED |
| - FBC 706.5 HORIZONTAL CONTINUITY. |
| FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO |
| EXTERIOR WALL AND SHALL EXTEND NOT LESS THAN 18 INCHES |
| (457 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. |
| EXCEPTIONS: (1) FIRE WALLS SHALL BE PERMITTED TO |
| TERMINATE AT THE INTERIOR SURFACE OF COMBUSTIBLE |
| EXTERIOR SHEATHING OR SIDING PROVIDED THE EXTERIOR WALL |
| HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR |
| FOR A HORIZONTAL DISTANCE OF NOT LESS THAN 4 FEET (1220 |
| MM) ON BOTH SIDES OF THE FIRE WALL. OPENINGS WITHIN |
| SUCH EXTERIOR WALLS SHALL BE PROTECTED BY OPENING |
| PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| THAN 3/4 HOUR. |
| |
| 4) DRAWING (A.03) - STAIR HAND RAIL EXTENSIONS NEED TO |
| CONTINUE IN THE DIRECTION OF THE STAIR - SHOULD NOT |
| TURN UNLESS THE STAIR CONTINUES - FBC 1014.6 HANDRAIL |
| EXTENSIONS.WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN |
| FLIGHTS, THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT |
| LESS THAN 12 INCHES (305 MM) BEYOND THE TOP RISER AND |
| CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE |
| BOTTOM RISER. |
| |
| 5) PLEASE PROVIDE A SURVEY. |