Plan Review Notes
Plan Review Notes For Permit 23020545
Permit Number 23020545
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-16 09:52:50JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER; TO CORRECT EXPOSURE
 CATEGORY, DESIGN PRESSURES & NAILING PATTERNS. THE
 EXPOSURE CATEGORY FOR 4311 N FLAGLER DR WEST PALM
 BEACH, FL 33407 IS EXPOSURE CATEGORY D.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL27499.20-R4 COVERS MULTIPLE INSTALLATION
 OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT INSTALLATION OPTION FROM PAGE #2 OF THE
 EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY D AREAS. (-147.). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R13
 HAS BEEN REVISED TO FL11602-R15. PLEASE NOTE: PRODUCT
 APPROVAL FL11602-R15 DO NOT HAVE A SYSTEM THAT MEET OR
 EXCEED -147 MINIMUM DESIGN PRESSURE FOR A GABLE ROOF;
 ZONE 3 WITH A ROOF SLOPE BETWEEN 2/12 & 4/12 IN AN
 EXPOSURE CATEGORY D AREA. PROVIDE UNDERLAYMENT SYSTEM
 THAT MEETS OR EXCEEDS THE ABOVE CRITERIA.
 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  