2023-02-21 08:49:511ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23020542
 2/21/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A PIPING INSTALLATION DIAGRAM BASED
 ON THE MANUFACTURER???S GUIDELINES- SEC. 1003.3.5 FBC
 P. THE SELECTED BK RESOURCES INTERCEPTOR IS PDI
 APPROVED AND TYPICAL INSTALLATION DIAGRAMS CAN BE FOUND
 ON PAGE 23 OF THE PDI G101- STANDARD. THE DIAGRAM SHALL
 INDICATE A TRAP FOR THE SINK, FLOW CONTROL AIR INTAKE,
 WASTE VENTING, AND DIRECT CONNECTION FROM THE OUTLET TO
 THE SANITARY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  