Plan Review Notes
Plan Review Notes For Permit 23020446
Permit Number 23020446
Review Stop E
Sequence Number 1
Notes
Date Text
2023-06-07 15:29:59FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF SERVICE EQUIPMENT DISCONNECT
 (SERVICE OVERCURRENT PROTECTION) AND SERVICE CONDUCTORS
 AS PER NEC 230.
  
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE.
 NEC 215.2, 220, 408.30
  
 3. PANEL SCHEDULE IN ACCORDANCE WITH NEC 408.4(A).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  