Plan Review Notes For Permit 23020399 |
Permit Number |
23020399 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-04-05 12:00:29 | ELECTRIC REVIEW FAILED | | | | 1) PREVIOUS COMMENT NOT ADDRESSED. PLEASE PROVIDE A | | WORK SCOPE AND NOTE ON PLANS NEW VERSUS EXISTING WORK. | | IF ALL ITEMS ON PLANS ARE NEW PLEASE STATE WITH A NOTE | | ALL WORK DETAILED IS NEW AND IS TO COMPLY WITH ALL | | CURRENT BUILDING AND ELECTRICAL CODES. FBC 107.2 | | 2)PLEASE PROVIDE PRINTED NAME AND SIGNATURE OF THE | | PERSON WHO PREPARED THE ELECTRICAL DESIGN SHALL BE ON | | THE DRAWINGS- SEC. 107.2.1 WPB. PLEASE NOTE THAT AN | | ELECTRICAL SUB-CONTRACTOR APPLICATION SHALL BE | | SUBMITTED TO THE WPB BUILDING DEPT.- SEC. 105.1 WPB. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|