Plan Review Notes
Plan Review Notes For Permit 23020399
Permit Number 23020399
Review Stop E
Sequence Number 2
Notes
Date Text
2023-04-05 12:00:29ELECTRIC REVIEW FAILED
  
 1) PREVIOUS COMMENT NOT ADDRESSED. PLEASE PROVIDE A
 WORK SCOPE AND NOTE ON PLANS NEW VERSUS EXISTING WORK.
 IF ALL ITEMS ON PLANS ARE NEW PLEASE STATE WITH A NOTE
 ALL WORK DETAILED IS NEW AND IS TO COMPLY WITH ALL
 CURRENT BUILDING AND ELECTRICAL CODES. FBC 107.2
 2)PLEASE PROVIDE PRINTED NAME AND SIGNATURE OF THE
 PERSON WHO PREPARED THE ELECTRICAL DESIGN SHALL BE ON
 THE DRAWINGS- SEC. 107.2.1 WPB. PLEASE NOTE THAT AN
 ELECTRICAL SUB-CONTRACTOR APPLICATION SHALL BE
 SUBMITTED TO THE WPB BUILDING DEPT.- SEC. 105.1 WPB.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  