2023-02-28 06:17:011ST REVIEW FMC
 PERMIT: 23020394
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL DRAWING DOES NOT SHOW THE REQUIRED
 OUTDOOR AIR DUCT DESIGN. PROVIDE THE REQUIRED OUTDOOR
 AIR DUCTWORK DESIGN FOR THE REQUIRED OUTDOOR AIR FOR
 THIS SYSTEM. FMC 601
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS SPACE
 ACCORDING TO THE OCCUPANT DENSITY AND OCCUPANCY
 CLASSIFICATION. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  