Plan Review Notes
Plan Review Notes For Permit 23020346
Permit Number 23020346
Review Stop E
Sequence Number 1
Notes
Date Text
2023-03-02 13:55:25ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL THE REQUIRED SMOKE/CARBON ALARM IN
 MASTER BEDROOM AS PER FBC RES 314 AND 315
  
 2) ENSURE RECEPTACLES MEET SPACING REQUIREMENTS AS PER
 NEC 210.52 IN FAMILY ROOM, LIVING ROOM, DOWNSTAIRS
 BEDROOM, UPSTAIRS BEDROOM 202, 218 AND 214.
  
 NEC 210.52 (1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET
  
 (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE
 SHALL INCLUDE THE FOLLOWING:
  
 (1) ANY SPACE (2 FT) OR MORE IN WIDTH (INCLUDING SPACE
 MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR
 LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE
 COUNTERTOPS OR SIMILAR WORK SURFACES
  
 (2) THE SPACE OCCUPIED BY FIXED PANELS IN WALLS,
 EXCLUDING SLIDING PANELS
  
 (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS
 FREESTANDING BAR-TYPE COUNTERS OR RAILINGS
  
 3) PLEASE CORRECT EGC SIZE TO INTERIOR 250-AMP ELECTRIC
 PANEL TO #4CU AS PER TABLE NEC 250.122
  
 4) PLEASE INDICATE ON ELECTRIC PLAN THE REQUIRED 3 FEET
 WORKING CLEARANCE IN FRONT OF THE OUTDOOR ELECTRIC
 SERVICE EQUIPMENT AS REQUIRE PER NEC 110.26 TABLE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  