2023-03-20 19:02:29 | BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23020329 |
| 345 SUMMA ST |
| |
| 1- PLANS SUBMITTED DON'T SHOW PROPOSED LOCATION OF |
| CANTILEVERED STRUCTURE. PROVIDE PLANS WITH PROPOSED |
| LOCATION. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- ENGINEER'S LETTER APPROVING OFFSET COLUMNS ON SPREAD |
| FOOTINGS: |
| A) LETTER NEEDS TO IDENTIFY THE CANTILEVERED STRUCTURE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) THE LETTER HAS A COPY OF THE ENGINEER'S |
| SEAL/SIGNATURE. NEED TO HAVE THE ORIGINAL SIGNATURE OF |
| THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 F.S. |
| WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| DRAWINGS AND LETTERS WERE SUBMITTED ELECTRONICALLY. |
| ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| SIGNATURE. |
| |
| ENGINEERS |
| 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |