Plan Review Notes
Plan Review Notes For Permit 23020290
Permit Number 23020290
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-13 15:39:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23020290
 2/13/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET T: THE INDEX ON THE TITLE SHEET SHOWS SHEETS
 P0.1 & P0.2 WHICH WERE NOT INCLUDED WITH THE PLAN SET
 FOR REVIEW. A COMPLETE REVIEW OF THE PLANS CANNOT BE
 ACCOMPLISHED WITHOUT A COMPLETE SET OF PLUMBING PLANS-
 SEC. 107.2.1 WPB. IT APPEARS THAT THE PLUMBING FIXTURE
 AND EQUIPMENT SCHEDULES ARE ON THOSE MISSING PLANS.
  
 2) SHEETS A211, P1.1 & P2.3: THE FLOOR SINKS RECEIVING
 DRAINAGE FROM ICE BINS #45 & 57 SHALL DISCHARGE INTO
 THE SANITARY SYSTEM AND NOT THE GREASE WASTE- SEC.
 1003.3.1 FBC P.
  
 3) P2.2 & P3.1: A MEANS OF LIMITING THE HOT WATER
 TEMPERATURE FROM THE WATER HEATERS OTHER THAN THE
 THERMOSTATS SHALL BE PROVIDED- SEC. 607.1. 1 FBC P.
 TYPICALLY A MASTER THERMOSTSTIC MIXING VALVE WILL BE
 INSTALLED. THIS REQUIREMENT IS IN ADDITION TO THE
 MIXING VALVES PROVIDED AT THE SINKS. PLEASE PROVIDE A
 DETAIL TO SHOW COMPLIANCE.
  
 4) P3.1: CORRECT THE GREASE WASTE CALCULATIONS SHOWING
 ICE MACHINE AND HAND SINK DRAINAGE INTO THE GREASE
 INTERCEPTOR. THE PLANS ARE CORRECTLY INDICATING THE
 DRAINAGE INTO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P.
  
 5) P1.1 & P2.3: PLEASE SHOW EXISTING OR NEW CLEANOUTS
 WILL BE INSTALLED AT THE AT THE JUNCTION OF THE
 SANITARY BUILDING DRAIN AND SEWER LINE- SEC. 708.1.3
 FBC P.
  
 6) A210: THERE APPEARS TO BE NUMEROUS ACCESSIBLE
 PLUMBING FIXTURE DETAILS MISSING INCLUDING THE
 FOLLOWING ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SEC. 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS FROM THE FINISHED
 FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 7) THE ENERGY EFFICIENCY REPORT DOES NOT PROVIDE PIPING
 SYSTEM COMPLIANCE DATA- SEC. C404.4 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  