 PLAN REVIEW RESULTS: DENIED.
  
  
 1) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 REFRIGERATION EQUIPMENT (WALK-IN COOLER AND FREEZER)
 WILL REQUIRE A SEPARATE PERMIT APPLICATION AND A
 SEPARATE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) SHEETS M1.2 AND M1.1: PROVIDE ON THE DRAWING HOW THE
 MECHANICAL UNITS ON THE ROOF AND EQUIPMENT DECK WILL BE
 ACCESSED FOR SERVICE AND REMOVAL. FMC 306.5
  
 3) SHEET M1.2: PROVIDE THE GUARD REQUIREMENTS FOR
 EQUIPMENT THAT IS WITHIN 10 FEET OF THE ROOFS EDGE. FMC
 304.11
  
 4) SHEET M1.1: SHOW THAT THE O/A DUCT TERMINATIONS
 KEYNOTES 1 AND 2, WILL MEET THE REQUIREMENTS OF FMC
 401.4 INTAKE OPENING LOCATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  