 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. PLEASE VERIFY & CORRECT; SUBMITTED
 AERIAL SITE MAP MUST SHOW INDICATES MRH 15 FT. PERMIT
 APPLICATION SCOPE OF WORK DESCRIBES REROOFING SECOND
 FLOOR FLAT ROOF WHICH WOULD HAVE A MINIMUM MRH 20 FT.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL10497-R8 SYSTEM NO. W-157 DO NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -138.57
 FOR EXPOSURE CATEGORY D AREAS WITH FLAT ROOF MRH 20 FT.
 PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN
 PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY D/PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH
 AN APPROVED SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  