2023-02-06 12:40:00 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 PLEASE CLARIFY; SUBMITTED APPROVED |
| DRAWINGS INDICATES REROOFING LOWER BARREL TILE ROOF |
| ONLY. IF ADDITIONAL REROOFING/ROOFING WILL BE PERFORMED |
| INDICATE ON ROOF DRAWING AND CLEARLY IDENTIFY AREAS TO |
| RECEIVE NEW ROOFING WITH ROOFING SYSTEM TO BE USED. |
| 2. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND |
| SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR |
| PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL |
| LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 20-0131.01 SYSTEM |
| TYPE A (2). PLEASE NOTE THIS PROJECT IS LOCATED IN AN |
| EXPOSURE D CATEGORY AREA. |
| 3. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND |
| SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR |
| PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL |
| LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 17-1003.15 SYSTEM |
| TYPE E (2). PLEASE NOTE THIS PROJECT IS LOCATED IN AN |
| EXPOSURE D CATEGORY AREA. |
| 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL2533-R28 SYSTEM NO. W-77 DO NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -131.42 |
| FOR EXPOSURE CATEGORY D AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY D/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. |
| 5. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11288-R21 |
| COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED |
| ATTACHMENT LIMITATION SYSTEM #14 PAGE #7 DO NOT MEET OR |
| EXCEED -85 MAXIMUM DESIGN PRESSURE REQUIREMENT. SELECT |
| SYSTEM THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| 6. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| SUBMITTING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |