2023-02-03 12:00:29 | 1ST REVIEW FMC |
| PERMIT: 23020072 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) ON THE REVISION REQUEST FORM UNDER DESCRIPTION OF |
| INFORMATION BEING SUBMITTED IT STATES ONLY SEE |
| MECHANICAL DRAWINGS. ON THE MECHANICAL DRAWING |
| SUBMITTED. IT APPEARS THE DIFFERENCE BETWEEN THE |
| ORIGINALLY APPROVED DRAWING AND THIS LATEST DRAWING IS |
| THE DUCT IS NOW WHAT APPEARS TO BE ALL FLEX DUCT. THERE |
| IS ALSO A NEW AIR CONDITIONING SYSTEM SCHEDULE THAT |
| INCLUDES AHU-1, AHU-2 AND AHU-3. ARE THESE TO BE NEW |
| INSTEAD OF EXISTING NOW? IF SO, THE DRAWING STILL HAS |
| THEM AS EXISTING, PLEASE CHANGE THIS. ALSO, ON THE |
| REVISION FORM THE INCREASED VALUE OF WORK IS NOT FILLED |
| IN. PROVIDE THE CORRECTED AMOUNT OF DOLLAR VALUE FOR |
| ALL CHANGES. PROVIDE A SCOPE OF WORK FOR ALL CHANGES TO |
| HELP THIS REVIEWER UNDERSTAND WHAT IS BEING CHANGED |
| UNDER THIS REVISION. FBC 107.3.5 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |