Plan Review Notes
Plan Review Notes For Permit 23020072
Permit Number 23020072
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-03 12:00:291ST REVIEW FMC
 PERMIT: 23020072
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ON THE REVISION REQUEST FORM UNDER DESCRIPTION OF
 INFORMATION BEING SUBMITTED IT STATES ONLY SEE
 MECHANICAL DRAWINGS. ON THE MECHANICAL DRAWING
 SUBMITTED. IT APPEARS THE DIFFERENCE BETWEEN THE
 ORIGINALLY APPROVED DRAWING AND THIS LATEST DRAWING IS
 THE DUCT IS NOW WHAT APPEARS TO BE ALL FLEX DUCT. THERE
 IS ALSO A NEW AIR CONDITIONING SYSTEM SCHEDULE THAT
 INCLUDES AHU-1, AHU-2 AND AHU-3. ARE THESE TO BE NEW
 INSTEAD OF EXISTING NOW? IF SO, THE DRAWING STILL HAS
 THEM AS EXISTING, PLEASE CHANGE THIS. ALSO, ON THE
 REVISION FORM THE INCREASED VALUE OF WORK IS NOT FILLED
 IN. PROVIDE THE CORRECTED AMOUNT OF DOLLAR VALUE FOR
 ALL CHANGES. PROVIDE A SCOPE OF WORK FOR ALL CHANGES TO
 HELP THIS REVIEWER UNDERSTAND WHAT IS BEING CHANGED
 UNDER THIS REVISION. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  