2023-02-09 13:02:37 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC 403.1.1 - PLEASE SHOW THE FIXTURE |
| CALCULATIONS AND THE SHOW THAT YOU ARE PROVIDING THE |
| MINIMUM NUMBER OF FIXTURES. |
| |
| 2. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A RISER DIAGRAM |
| THAT INCLUDES THE DRAIN, WASTE AND VENT SYSTEM AND THE |
| WATER DISTRIBUTION SYSTEM. |
| |
| 3. 2017 WPB AMENDS 107.3.5.1.3 - SHOW THE LOCATION OF |
| THE WATER HEATER AND INCLUDE DETAILS FOR A MIXING VALVE |
| PER FPC 607.1.1 INSTALLED AT THE HEAT SOURCE PER 613.1. |
| |
| 4. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A ROOF DRAINAGE |
| PLAN INCLUDE GALLONS PER MINUTE, LEADER/DRAIN SIZES. |
| DRAIN PIPING PLAN, OVERFLOW/SCUPPER SIZES ETC. |
| |
| 5. 2017 WPB AMENDS 107.3.5.1.3 - BE AWARE THAT IF |
| IRRIGATION IS INSTALLED, IT WILL REQUIRE A SEPARATE |
| PERMIT. |
| |
| 6. 2017 WPB AMENDS 107.3.5.1.3 - SITE PLAN SHOWING THE |
| LOCATION OF THE WATER SERVICE, SEWER SERVICE, GREASE |
| TRAPS, BACKFLOWS, ETC. |
| |
| 7. 2020 FPC 607.2 - PROVIDE A CIRCULATING LOOP IF THE |
| LENGTH OF THE HOT WATER SUPPLY EXCEEDS 50 FEET. IF A |
| RETURN LOOP IS PROVIDED, THE RETURN SHALL BE IN |
| COMPLIANCE WITH 2020 FPC 607.2.2 AND RETURN TO THE COLD |
| WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER |
| INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| THERMOSTATIC MIXING VALVE. |
| |
| 8. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE |
| AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE |
| SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR |
| PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected]. AFTER YOU HAVE THE PERMIT(S) |
| GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| LETTER AND I WILL COMPLY THIS COMMENT. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |