Plan Review Notes
Plan Review Notes For Permit 23020041
Permit Number 23020041
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-09 13:02:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - PLEASE SHOW THE FIXTURE
 CALCULATIONS AND THE SHOW THAT YOU ARE PROVIDING THE
 MINIMUM NUMBER OF FIXTURES.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A RISER DIAGRAM
 THAT INCLUDES THE DRAIN, WASTE AND VENT SYSTEM AND THE
 WATER DISTRIBUTION SYSTEM.
  
 3. 2017 WPB AMENDS 107.3.5.1.3 - SHOW THE LOCATION OF
 THE WATER HEATER AND INCLUDE DETAILS FOR A MIXING VALVE
 PER FPC 607.1.1 INSTALLED AT THE HEAT SOURCE PER 613.1.
  
 4. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A ROOF DRAINAGE
 PLAN INCLUDE GALLONS PER MINUTE, LEADER/DRAIN SIZES.
 DRAIN PIPING PLAN, OVERFLOW/SCUPPER SIZES ETC.
  
 5. 2017 WPB AMENDS 107.3.5.1.3 - BE AWARE THAT IF
 IRRIGATION IS INSTALLED, IT WILL REQUIRE A SEPARATE
 PERMIT.
  
 6. 2017 WPB AMENDS 107.3.5.1.3 - SITE PLAN SHOWING THE
 LOCATION OF THE WATER SERVICE, SEWER SERVICE, GREASE
 TRAPS, BACKFLOWS, ETC.
  
 7. 2020 FPC 607.2 - PROVIDE A CIRCULATING LOOP IF THE
 LENGTH OF THE HOT WATER SUPPLY EXCEEDS 50 FEET. IF A
 RETURN LOOP IS PROVIDED, THE RETURN SHALL BE IN
 COMPLIANCE WITH 2020 FPC 607.2.2 AND RETURN TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
  
 8. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved