2023-06-15 08:34:23PLAN DENIED
 1) PAGE M1.00 REFER TO SECTION 503.1 EXHAUST DISCHARGE.
 EF-2 IS DISCHARGEING INTO THE GARAGE.
 2) PAGE M1.01 WHAT IS THE 10X8 DUCT IN THE CORRIDOR?
 IS THAT THE AIR HANDLER OR SOME KIND OF EXHAUST. THE
 LEGEND THE SIMBOL SAYS EXHAUST. SECTION 107 FBC
 3) REFER TO SECTION 402.2 VENTILATION AREA REQUIRED.
 2020FBC (M) FOR LIVE IN UNITS.
 4) PAGE M6.00 CAN'T READ THE NATURL VEMTILATION
 CALCULATIONS FOR THE LIVE IN UNITS SECTION 107 FBC
 5) REFER TO SECTION 504.8.4.1 SPECIFIED LENGTH
 AND TABLE 504.8.4.1 2020 FBC (M). CLOTHES
 DRYER EXHAUXT DUCT.