2023-06-02 14:31:19 | ELECTRIC REVIEW FAILED |
| |
| 1) GENERATOR IS STILL DETAILED ON GROUND FLOOR PLAN |
| ALTHOUGH IT WAS REMOVED. PLEASE REMOVE ALL REFERENCES |
| TO GENERATOR. FBC 107.2 |
| |
| 2) RISER DOES NOT DETAIL PANEL P, RISER INDICATES PANEL |
| P WITH A MLO SYMBOL, RISER INDICATES PANEL P ON 5TH |
| FLOOR, HOWEVER, PANEL P IS SHOWN TO BE LOCATED POOL |
| EQUIPMENT RM 242, PANEL P OCP IS NOT SHOWN ON THE RISER |
| AS BEING IN THE MDP PANEL, PANEL OPG IS DETAILED IN MDP |
| PANEL SCHEDULE WITH 600 OCP OTHER SCHEDULES AND RISER |
| INDICATE 400 AMP. NEC 215.5 |
| |
| 3) PLEASE CHANGE THE NAME IN THE SUBMITTAL FOR SHEET |
| E7.03 FROM FIRE ALARM RISER DIAGRAM TO BUILDING |
| ELECTRIC LOAD CALCULATIONS IN THE SUBMITTAL. |
| |
| 4) PLEASE PROVIDE PANEL SCHEDULES FOR PANELS EP4, WP2 |
| ANDWP4. FBC 107.2 |
| |
| 5) COMPLETE MOTOR/EQUIPMENT CIRCUIT SCHEDULE TO INCLUDE |
| PANEL ORIGIN FOR EQUIPMENT SHOWN. PLEASE REMOVE FP AS |
| IT DOES NOT EXIST. FBC 107.2 |
| |
| 6) PLEASE DETAIL THAT EV CHARGING STATIONS PROVIDE ONE |
| EV CHARGING STATION STRIPED AS AN ACCESSIBLE PARKING |
| SPACE. ONE SUCH SPACE IS REQUIRED FOR EVERY 25 EV |
| CHARGING STATIONS PROVIDED. SECTION 208 OF FLORIDA |
| ACCESSIBILITY CODE REQUIRES THAT EACH TYPE OF PARKING |
| FACILITY (SUCH AS COVERED PARKING, PARKING WITH |
| CHARGING STATION, ETC.) MUST ALSO INCLUDE ACCESSIBLE |
| PARKING, AND THE NUMBER OF ACCESSIBLE SPACES REQUIRED |
| IS DETERMINED BY HOW MANY REGULAR (NON-ACCESSIBLE) |
| PARKING SPACES OF THAT TYPE ARE PROVIDED. IF THERE ARE |
| BETWEEN 1 - 25 PARKING SPACES PROVIDED WITH CHARGING |
| STATIONS (I.E. PARKING FACILITY), THEN 1 SUCH SPACE |
| MUST BE ACCESSIBLE |
| |
| 7) APARTMENT ELECTRIC FLOOR PLANS AND PANEL SCHEDULES |
| DO NOT DETAIL THE REQUIRED 2 SMALL APPLIANCE CIRCUITS |
| IN ACCORDANCE WITH NEC 21O.11(C)(1) |
| |
| 8) PLEASE LOCATE POOL ALL POOL EQUIPMENT, PUMP, HEATER, |
| ETC. ON ELECTRIC FLOOR PLANS. FBC 107.2 |
| |
| 9) PLEASE INDICATE DISTANCE OF RECEPTACLE NEAR POOL AS |
| BEING COMPLIANT WITH NEC 680.22(A)(1) |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |