Plan Review Notes
Plan Review Notes For Permit 23020018
Permit Number 23020018
Review Stop E
Sequence Number 2
Notes
Date Text
2023-06-02 14:31:19ELECTRIC REVIEW FAILED
  
 1) GENERATOR IS STILL DETAILED ON GROUND FLOOR PLAN
 ALTHOUGH IT WAS REMOVED. PLEASE REMOVE ALL REFERENCES
 TO GENERATOR. FBC 107.2
  
 2) RISER DOES NOT DETAIL PANEL P, RISER INDICATES PANEL
 P WITH A MLO SYMBOL, RISER INDICATES PANEL P ON 5TH
 FLOOR, HOWEVER, PANEL P IS SHOWN TO BE LOCATED POOL
 EQUIPMENT RM 242, PANEL P OCP IS NOT SHOWN ON THE RISER
 AS BEING IN THE MDP PANEL, PANEL OPG IS DETAILED IN MDP
 PANEL SCHEDULE WITH 600 OCP OTHER SCHEDULES AND RISER
 INDICATE 400 AMP. NEC 215.5
  
 3) PLEASE CHANGE THE NAME IN THE SUBMITTAL FOR SHEET
 E7.03 FROM FIRE ALARM RISER DIAGRAM TO BUILDING
 ELECTRIC LOAD CALCULATIONS IN THE SUBMITTAL.
  
 4) PLEASE PROVIDE PANEL SCHEDULES FOR PANELS EP4, WP2
 ANDWP4. FBC 107.2
  
 5) COMPLETE MOTOR/EQUIPMENT CIRCUIT SCHEDULE TO INCLUDE
 PANEL ORIGIN FOR EQUIPMENT SHOWN. PLEASE REMOVE FP AS
 IT DOES NOT EXIST. FBC 107.2
  
 6) PLEASE DETAIL THAT EV CHARGING STATIONS PROVIDE ONE
 EV CHARGING STATION STRIPED AS AN ACCESSIBLE PARKING
 SPACE. ONE SUCH SPACE IS REQUIRED FOR EVERY 25 EV
 CHARGING STATIONS PROVIDED. SECTION 208 OF FLORIDA
 ACCESSIBILITY CODE REQUIRES THAT EACH TYPE OF PARKING
 FACILITY (SUCH AS COVERED PARKING, PARKING WITH
 CHARGING STATION, ETC.) MUST ALSO INCLUDE ACCESSIBLE
 PARKING, AND THE NUMBER OF ACCESSIBLE SPACES REQUIRED
 IS DETERMINED BY HOW MANY REGULAR (NON-ACCESSIBLE)
 PARKING SPACES OF THAT TYPE ARE PROVIDED. IF THERE ARE
 BETWEEN 1 - 25 PARKING SPACES PROVIDED WITH CHARGING
 STATIONS (I.E. PARKING FACILITY), THEN 1 SUCH SPACE
 MUST BE ACCESSIBLE
  
 7) APARTMENT ELECTRIC FLOOR PLANS AND PANEL SCHEDULES
 DO NOT DETAIL THE REQUIRED 2 SMALL APPLIANCE CIRCUITS
 IN ACCORDANCE WITH NEC 21O.11(C)(1)
  
 8) PLEASE LOCATE POOL ALL POOL EQUIPMENT, PUMP, HEATER,
 ETC. ON ELECTRIC FLOOR PLANS. FBC 107.2
  
 9) PLEASE INDICATE DISTANCE OF RECEPTACLE NEAR POOL AS
 BEING COMPLIANT WITH NEC 680.22(A)(1)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  