Plan Review Notes
Plan Review Notes For Permit 23020018
Permit Number 23020018
Review Stop B
Sequence Number 2
Notes
Date Text
2023-06-02 16:43:08PLAN REVIEW COMMENTS
  
 23020018
 512 CLEMATIS STREET
 5 STORY
 III-B CONSTRUCTION TYPE
 88 APARTMENTS
 MIXED USE
 THRESHOLD BUILDING
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) [PARTIALLY RESOLVED.] THIS PROJECT IS A THRESHOLD
 BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7)
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) RESOLVED.
  
 B) [THE REQUIRED THRESHOLD FORMS HAVE NOT BEEN
 SUBMITTED.] THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 C) [THE REQUIRED THRESHOLD BUILDING STATEMENT IS
 MISSING FROM SOME OF THE STRUCTURAL PAGES. IT IS
 REQUIRED TO BE ON ALL OF THE STRUCTURAL PLAN SHEETS.]
 THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) [THIS HAS NOT BEEN SUBMITTED.] FOR THE SPECIAL
 INSPECTOR PLEASE PROVIDE A RESUME OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECT. THE RESUME MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME. AFTER THE RESUME IS REVIEWED, AN INTERVIEW WILL
 BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN INSPECTOR
 BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING THE ABOVE
 CRITERIA.
  
 E) [THIS HAS NOT BEEN SUBMITTED.] THE CONTRACTOR WILL
 PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF
 CONSTRUCTION.
  
 F) RESOLVED.
  
 G) [PROVISO. TO BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTAL TO THIS OFFICE.]
 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, PLANS
 AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) RESOLVED.
  
 I) RESOLVED.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS IF
 YOU NEED IT.
  
 3) [NOT RESOLVED.] SUBMIT A MANAGEMENT OF TRAFFIC (MOT)
 PLAN, INCLUDING PROTECTION OF PEDESTRIANS. FBC 3301
  
 4) [NOT RESOLVED.] SHOW HOW THE ADJOINING PROPERTIES
 WILL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION PER
 FBC 3307.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 7) RESOLVED.
  
 8) RESOLVED.
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED.
  
 15) RESOLVED.
  
 16) RESOLVED.
  
 17) [NOT RESOLVED. THE STATEMENT NEEDS TO BE ON THE
 PLANS. IT SHOULD STATE THAT THIS POOL IS LIMITED TO THE
 EXCLUSIVE USE OF RESIDENTS AND THEIR GUESTS.] SHOW HOW
 THE SPA POOL WILL COMPLY WITH FBC ACCESSIBILITY SECTION
 242.2 SWIMMING POOLS. AT LEAST TWO ACCESSIBLE MEANS OF
 ENTRY SHALL BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE
 MEANS OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING
 WITH 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3;
 TRANSFER WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS
 COMPLYING WITH 1009.5; AND POOL STAIRS COMPLYING WITH
 1009.6. AT LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED
 SHALL COMPLY WITH 1009.2 OR 1009.3.
 EXCEPTIONS:
 1. WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET
 (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE
 ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED
 THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL
 LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING
 WITH 1009.3.
 2. WAVE ACTION POOLS, LEISURE RIVERS, SAND BOTTOM
 POOLS, AND OTHER POOLS WHERE USER ACCESS IS LIMITED TO
 ONE AREA SHALL NOT BE REQUIRED TO PROVIDE MORE THAN ONE
 ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE ACCESSIBLE
 MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH
 1009.2, A SLOPED ENTRY COMPLYING WITH 1009.3, OR A
 TRANSFER SYSTEM COMPLYING WITH 1009.5.
 3. CATCH POOLS SHALL NOT BE REQUIRED TO PROVIDE AN
 ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE CATCH POOL
 EDGE IS ON AN ACCESSIBLE ROUTE.
  
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 18) [NOT RESOLVED.] SUBMIT A DETAILED COST BREAKDOWN
 FOR THIS PROJECT. THIS WILL PREVENT US FROM CHARGING
 YOU DOUBLE FOR ITEMS THAT REQUIRE SEPARATE PERMITS.
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 19) [PROVISO.] COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON THE STRUCTURAL PLANS PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 B. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 C. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED
 PRIOR TO C.O.
  
 D. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE
 SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE
 ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED
 PRIOR TO CONCRETE POUR.
  
 E. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS
 REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION.
  
 F. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
 20) RESOLVED.
  
 21) [PARTIALLY RESOLVED. THE 12' DISTANCE FROM THE
 BUILDING TO THE CENTERLINE OF THE ALLEY IS SHOWN ON
 SHEET SP.0.1, NOT A1.1.2. THE RESPONSE LETTER STATES
 THAT THE OPENING AREA CALCULATIONS FOR THE SOUTH
 ELEVATION IS ON SHEET A3.0.1, HOWEVER, SHEET A8.1.1 WAS
 UPLOADED IN THE FILE FOR THIS SHEET. BASED ON THE 12'
 DISTANCE TO THE ALLY CENTERLINE THE PERCENT OF WALL
 AREA OPENINGS IS 45 PERCENT PER STORY.] SHOW THE
 CALCULATIONS FOR THE ALLOWABLE AREA OF OPENINGS FOR
 EACH STORY OF THE SOUTH ELEVATION AS REQUIRED BY FBC
 705.8.1. SHOW THE DISTANCE FROM THE WEST WALL TO THE
 CENTER OF THE ALLY ON THE PLANS.
  
 22) [NOT RESOLVED. THE AREA BREAKDOWN OF THE THIRD
 FLOOR IS MISSING SOME OF THE R-2 UNITS.] PROVIDE A
 FLOOR AREA BREAKDOWN BY OCCUPANCY TYPE FOR EACH FLOOR
 OF THE PROPOSED BUILDING. FBC 107.2.1 & 503.1
  
 23) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. THE
 RESPONSES TO THESE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 NEW COMMENTS:
  
 24) THE ENERGY COMPLIANCE DOCUMENT HAS THE NUMBER OF
 STORIES AS ONE AND THIS IS A FIVE STORY BUILDING. FBC
 107.2.1
  
 25) THERE APPEARS TO BE SOME DISCREPANCIES BETWEEN THE
 GROSS BUILDING AREA (68,296 SQFT) SPECIFIED ON THE
 PLANS AND THE TOTAL AREA (98,073 SQFT) ON THE ENERGY
 FORM. FBC 107.2.1
  
  
  
  
  
  
  
  
  
  
  
  