2023-06-02 16:43:08 | PLAN REVIEW COMMENTS |
| |
| 23020018 |
| 512 CLEMATIS STREET |
| 5 STORY |
| III-B CONSTRUCTION TYPE |
| 88 APARTMENTS |
| MIXED USE |
| THRESHOLD BUILDING |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) RESOLVED. |
| |
| 2) [PARTIALLY RESOLVED.] THIS PROJECT IS A THRESHOLD |
| BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7) |
| "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| A) RESOLVED. |
| |
| B) [THE REQUIRED THRESHOLD FORMS HAVE NOT BEEN |
| SUBMITTED.] THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 |
| W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR |
| THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. |
| |
| C) [THE REQUIRED THRESHOLD BUILDING STATEMENT IS |
| MISSING FROM SOME OF THE STRUCTURAL PAGES. IT IS |
| REQUIRED TO BE ON ALL OF THE STRUCTURAL PLAN SHEETS.] |
| THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| |
| D) [THIS HAS NOT BEEN SUBMITTED.] FOR THE SPECIAL |
| INSPECTOR PLEASE PROVIDE A RESUME OF INSPECTION |
| EXPERIENCE ON PREVIOUS PROJECT. THE RESUME MUST BE |
| ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN. |
| THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE |
| RESUME. AFTER THE RESUME IS REVIEWED, AN INTERVIEW WILL |
| BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN INSPECTOR |
| BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING THE ABOVE |
| CRITERIA. |
| |
| E) [THIS HAS NOT BEEN SUBMITTED.] THE CONTRACTOR WILL |
| PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF |
| CONSTRUCTION. |
| |
| F) RESOLVED. |
| |
| G) [PROVISO. TO BE REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD BEFORE SUBMITTAL TO THIS OFFICE.] |
| 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, PLANS |
| AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| H) RESOLVED. |
| |
| I) RESOLVED. |
| |
| J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER |
| 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS IF |
| YOU NEED IT. |
| |
| 3) [NOT RESOLVED.] SUBMIT A MANAGEMENT OF TRAFFIC (MOT) |
| PLAN, INCLUDING PROTECTION OF PEDESTRIANS. FBC 3301 |
| |
| 4) [NOT RESOLVED.] SHOW HOW THE ADJOINING PROPERTIES |
| WILL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION PER |
| FBC 3307. |
| |
| 5) RESOLVED. |
| |
| 6) RESOLVED. |
| |
| 7) RESOLVED. |
| |
| 8) RESOLVED. |
| |
| 9) RESOLVED. |
| |
| 10) RESOLVED. |
| |
| 11) RESOLVED. |
| |
| 12) RESOLVED. |
| |
| 13) RESOLVED. |
| |
| 14) RESOLVED. |
| |
| 15) RESOLVED. |
| |
| 16) RESOLVED. |
| |
| 17) [NOT RESOLVED. THE STATEMENT NEEDS TO BE ON THE |
| PLANS. IT SHOULD STATE THAT THIS POOL IS LIMITED TO THE |
| EXCLUSIVE USE OF RESIDENTS AND THEIR GUESTS.] SHOW HOW |
| THE SPA POOL WILL COMPLY WITH FBC ACCESSIBILITY SECTION |
| 242.2 SWIMMING POOLS. AT LEAST TWO ACCESSIBLE MEANS OF |
| ENTRY SHALL BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE |
| MEANS OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING |
| WITH 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; |
| TRANSFER WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS |
| COMPLYING WITH 1009.5; AND POOL STAIRS COMPLYING WITH |
| 1009.6. AT LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED |
| SHALL COMPLY WITH 1009.2 OR 1009.3. |
| EXCEPTIONS: |
| 1. WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET |
| (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED |
| THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL |
| LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING |
| WITH 1009.3. |
| 2. WAVE ACTION POOLS, LEISURE RIVERS, SAND BOTTOM |
| POOLS, AND OTHER POOLS WHERE USER ACCESS IS LIMITED TO |
| ONE AREA SHALL NOT BE REQUIRED TO PROVIDE MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE ACCESSIBLE |
| MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH |
| 1009.2, A SLOPED ENTRY COMPLYING WITH 1009.3, OR A |
| TRANSFER SYSTEM COMPLYING WITH 1009.5. |
| 3. CATCH POOLS SHALL NOT BE REQUIRED TO PROVIDE AN |
| ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE CATCH POOL |
| EDGE IS ON AN ACCESSIBLE ROUTE. |
| |
| COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE |
| RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL |
| FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO |
| THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT |
| COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, |
| INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. |
| IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY |
| IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS |
| REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON |
| THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER |
| STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. |
| |
| 18) [NOT RESOLVED.] SUBMIT A DETAILED COST BREAKDOWN |
| FOR THIS PROJECT. THIS WILL PREVENT US FROM CHARGING |
| YOU DOUBLE FOR ITEMS THAT REQUIRE SEPARATE PERMITS. |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 19) [PROVISO.] COMPONENT & CLADDING PRODUCT APPROVALS |
| REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO |
| THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO |
| INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN |
| ON THE STRUCTURAL PLANS PRIOR TO SUBMITTAL. IF PRODUCT |
| APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED, |
| ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM |
| DESIGN PRESSURES. |
| |
| B. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| REQUIRED FOR: |
| LIGHT POLES/SITE LIGHTING |
| FIRE ALARM |
| FIRE SPRINKLER |
| LOW VOLTAGE |
| ACCESS |
| LANDSCAPING |
| IRRIGATION |
| PARKING LOT |
| SWIMMING POOLS AND SPAS |
| GENERATORS |
| ALL OTHER ITEMS OTHER THAN BMEP |
| |
| C. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| PRIOR TO C.O. |
| |
| D. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE |
| SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE |
| ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED |
| PRIOR TO CONCRETE POUR. |
| |
| E. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS |
| REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. |
| |
| F. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| |
| 20) RESOLVED. |
| |
| 21) [PARTIALLY RESOLVED. THE 12' DISTANCE FROM THE |
| BUILDING TO THE CENTERLINE OF THE ALLEY IS SHOWN ON |
| SHEET SP.0.1, NOT A1.1.2. THE RESPONSE LETTER STATES |
| THAT THE OPENING AREA CALCULATIONS FOR THE SOUTH |
| ELEVATION IS ON SHEET A3.0.1, HOWEVER, SHEET A8.1.1 WAS |
| UPLOADED IN THE FILE FOR THIS SHEET. BASED ON THE 12' |
| DISTANCE TO THE ALLY CENTERLINE THE PERCENT OF WALL |
| AREA OPENINGS IS 45 PERCENT PER STORY.] SHOW THE |
| CALCULATIONS FOR THE ALLOWABLE AREA OF OPENINGS FOR |
| EACH STORY OF THE SOUTH ELEVATION AS REQUIRED BY FBC |
| 705.8.1. SHOW THE DISTANCE FROM THE WEST WALL TO THE |
| CENTER OF THE ALLY ON THE PLANS. |
| |
| 22) [NOT RESOLVED. THE AREA BREAKDOWN OF THE THIRD |
| FLOOR IS MISSING SOME OF THE R-2 UNITS.] PROVIDE A |
| FLOOR AREA BREAKDOWN BY OCCUPANCY TYPE FOR EACH FLOOR |
| OF THE PROPOSED BUILDING. FBC 107.2.1 & 503.1 |
| |
| 23) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. THE |
| RESPONSES TO THESE COMMENTS MAY RESULT IN ADDITIONAL |
| COMMENTS. |
| |
| NEW COMMENTS: |
| |
| 24) THE ENERGY COMPLIANCE DOCUMENT HAS THE NUMBER OF |
| STORIES AS ONE AND THIS IS A FIVE STORY BUILDING. FBC |
| 107.2.1 |
| |
| 25) THERE APPEARS TO BE SOME DISCREPANCIES BETWEEN THE |
| GROSS BUILDING AREA (68,296 SQFT) SPECIFIED ON THE |
| PLANS AND THE TOTAL AREA (98,073 SQFT) ON THE ENERGY |
| FORM. FBC 107.2.1 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |