Date |
Text |
2023-02-14 11:44:55 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE |
| AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE |
| SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR |
| PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected]. AFTER YOU HAVE THE PERMIT(S) |
| GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| LETTER AND I WILL COMPLY THIS COMMENT. |
| A) PLEASE PROVIDE A PROJECTED GREASE CALCULATION WITH |
| INTERCEPTOR DETAILS |
| B) THE GREASE WASTE HAS ONLY ONE RISER. IF IT IS THE |
| INTENT TO PROVIDE GREASE WASTE ACCESS TO ALL THREE |
| STORE FRONTS, SHOW CONTINUATION TO ALL THREE . |
| |
| 2. PAGE P4.01 - DETAIL #4/PAGE P7.04 - DETAIL #2 - UNIT |
| K -- BATHROOM GROUP - 2020 FPC 912.2.1 - ONLY ONE |
| FIXTURE IS ALLOWED TO BE UPSTREAM OF THE VENTED |
| FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT. |
| CURRENTLY, THE SHOWER AND WATER CLOSET ARE BOTH |
| UPSTREAM. |
| |
| 3. PAGE P4.01 - DETAIL #5/PAGE P7.04 - DETAIL #3 - UNIT |
| L -- BATHROOM GROUP - 2020 FPC 912.2.1 - ONLY ONE |
| FIXTURE IS ALLOWED TO BE UPSTREAM OF THE VENTED |
| FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT. |
| CURRENTLY, THE SHOWER AND WATER CLOSET ARE BOTH |
| UPSTREAM. |
| |
| 4. PAGE P4.01 - DETAIL #5/PAGE P7.04 - DETAIL #3 - UNIT |
| L - S-1 -- 2020 FPC 909.2 - THE KITCHEN DRAIN IS |
| NON-COMPLIANT. THE FALL OF THE FIXTURE DRAIN CANNOT |
| EXCEED THE DIAMETER OF THE PIPE, NOR CAN THE VENT |
| CONNECTION BE BELOW THE WEIR OF THE TRAP. ALSO, THE |
| VENT CONNECTION FROM THE DRAIN TO THE VENT STACK MUST |
| RISE VERTICALLY 6" ABOVE THE FLOOD RIM OF THE |
| FIXTURE(S) SERVED BEFORE GOING HORIZONTAL PER 905.4. |
| |
| 5. PAGE P4.01 - DETAIL #6/PAGE P7.04 - DETAIL #4 - UNIT |
| M -- BATHROOM GROUP - THE FLOOR PLAN ON PAGE 4.01 #6 |
| DOES NOT MATCH THE ISOMETRIC ON PAGE P7.01 - THE FLOOR |
| PLAN HAS THIS PROBLEM BUT THE ISOMETRIC IS DRAWN |
| CORRECTLY. CORRECT THE DRAWING ON P4.01 TO HAVE ONLY |
| ONE TRAP UPSTREAM OF THE VENTED FIXTURE'S CONNECTION. |
| 2020 FPC 912.2.1 - ONLY ONE FIXTURE IS ALLOWED TO BE |
| UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE |
| HORIZONTAL WET VENT. CURRENTLY, THE SHOWER AND WATER |
| CLOSET ARE BOTH UPSTREAM. |
| |
| 6. SEVERAL PLACES THROUGHOUT THE WATER RISERS THE HW |
| AND CW ARE MISLABLED AND CRISS CROSSED. CHECK FOR |
| ACCURACY. |
| |
| 7. P7.00 DETAIL #1 - OVERALL SANITARY RISER - PLEASE |
| ADD THE VENT STACKS TO THE SANITARY RISER. |
| |
| 8. P7.01 DETAIL #1 -- 2017 WPB AMENDS 107.3.5.1.3 - FOR |
| CLARITY, WHERE DO THE CONDENSATE RISERS TERMINATE? THEY |
| NEED TO BE VENTED AND VENTS NEED TO TERMINATE IN |
| ACCORDANCE WITH 903, |
| |
| 9. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE DETAIL THE |
| STORM RISERS FOR ROOF DRAINAGE AND INCLUDE THE GPM FOR |
| EACH RISER AND HORIZONTAL. |
| |
| 10. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A DETAIL FOR THE |
| SUMP PUMP FOR THE ELEVATOR SHAFTS THAT INCLUDES THE OIL |
| ALARM OR INTERCEPTOR REQUIRED BY 1003.4. |
| |
| 11. 2020 FPC 403.1.1 - FLOORS 1 APPEARS TO HAVE A |
| REQUIREMENT FOR TWO BATHROOMS, 1 MALE AND 1 FEMALE. |
| ONLY ONE IS PROVIDED. PER 403.2.1 - YOU COULD PROVIDE |
| FAMILY OR ASSISTED-USE TOILET FACILITIES, BUT STILL ARE |
| REQUIRED TO PROVIDE 2 BATHROOMS. |
| |
| 12. 2020 FPC 403.1.1 - FLOOR 2 - THE OCCUPANT LOAD |
| REQUIRES MORE WATER CLOSETS THAN THOSE PROVIDED. |
| |
| 13. 2020 FPC 403.1.1 - FLOOR 3 - THE OCCUPANT LOAD |
| TABLE HAS 2ND FLOOR IN THE COLUMN TO THE LEFT BUT IS |
| FOR FLOOR 3. AND IT APPEARS THAT THE OCCUPANT LOAD |
| NEEDS TO BE RECONFIGURED. IT DOES NOT APPEAR TO BE |
| ACCURATE. PLEASE CHECK AND RECONFIGURE. |
| |
| 14. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE INCLUDE THE |
| HOT WATER PIPING DETAILS AND WHERE THE HOT WATER SOURCE |
| WILL BE. |
| |
| 15. PAGE A1.2.2 - POOL EQUIP. - 2017 WPB AMENDS |
| 107.3.5.1.3 - ALTHOUGH THE POOL WILL BE ON A SEPARATE |
| PERMIT, PLEASE DETAIL A COMPLIANT DRAIN FOR THE |
| DISCHARGE OF THE POOL EQUIPMENT. |
| NOTE FOR POOL DISCHARGE: |
| SEC 90 - 205 EXCEPTIONS TO DISCHARGING POOL WASTE INTO |
| STORM WATER SYSTEM |
| SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO |
| SANITARY SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC |
| UTILITIES DEPARTMENT. |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORM WATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| - FOR STORM WATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 16. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND |
| SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR |
| PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE |
| DEVICE SHOULD CONFORM TO ASSE 1070. |
| |
| 17. 2017 WPB AMENDS 107.3.5.1.3 - INCLUDE IN THE |
| FIXTURE SCHEDULE THE FIXTURES FOR THE RESIDENTIAL |
| UNITS, WATER SUB-METERS, COMMON WATER HEATER, ETC. |
| |
| 18. 2017 WPB AMENDS 107.3.5.1.3 - TYPICALLY THERE ARE |
| EXTERIOR HOSE BIBS, IF APPLICABLE, ADD THESE TO THE |
| PLAN. |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |