Plan Review Notes
Plan Review Notes For Permit 23020018
Permit Number 23020018
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-14 11:44:551ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
 A) PLEASE PROVIDE A PROJECTED GREASE CALCULATION WITH
 INTERCEPTOR DETAILS
 B) THE GREASE WASTE HAS ONLY ONE RISER. IF IT IS THE
 INTENT TO PROVIDE GREASE WASTE ACCESS TO ALL THREE
 STORE FRONTS, SHOW CONTINUATION TO ALL THREE .
  
 2. PAGE P4.01 - DETAIL #4/PAGE P7.04 - DETAIL #2 - UNIT
 K -- BATHROOM GROUP - 2020 FPC 912.2.1 - ONLY ONE
 FIXTURE IS ALLOWED TO BE UPSTREAM OF THE VENTED
 FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT.
 CURRENTLY, THE SHOWER AND WATER CLOSET ARE BOTH
 UPSTREAM.
  
 3. PAGE P4.01 - DETAIL #5/PAGE P7.04 - DETAIL #3 - UNIT
 L -- BATHROOM GROUP - 2020 FPC 912.2.1 - ONLY ONE
 FIXTURE IS ALLOWED TO BE UPSTREAM OF THE VENTED
 FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT.
 CURRENTLY, THE SHOWER AND WATER CLOSET ARE BOTH
 UPSTREAM.
  
 4. PAGE P4.01 - DETAIL #5/PAGE P7.04 - DETAIL #3 - UNIT
 L - S-1 -- 2020 FPC 909.2 - THE KITCHEN DRAIN IS
 NON-COMPLIANT. THE FALL OF THE FIXTURE DRAIN CANNOT
 EXCEED THE DIAMETER OF THE PIPE, NOR CAN THE VENT
 CONNECTION BE BELOW THE WEIR OF THE TRAP. ALSO, THE
 VENT CONNECTION FROM THE DRAIN TO THE VENT STACK MUST
 RISE VERTICALLY 6" ABOVE THE FLOOD RIM OF THE
 FIXTURE(S) SERVED BEFORE GOING HORIZONTAL PER 905.4.
  
 5. PAGE P4.01 - DETAIL #6/PAGE P7.04 - DETAIL #4 - UNIT
 M -- BATHROOM GROUP - THE FLOOR PLAN ON PAGE 4.01 #6
 DOES NOT MATCH THE ISOMETRIC ON PAGE P7.01 - THE FLOOR
 PLAN HAS THIS PROBLEM BUT THE ISOMETRIC IS DRAWN
 CORRECTLY. CORRECT THE DRAWING ON P4.01 TO HAVE ONLY
 ONE TRAP UPSTREAM OF THE VENTED FIXTURE'S CONNECTION.
 2020 FPC 912.2.1 - ONLY ONE FIXTURE IS ALLOWED TO BE
 UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE
 HORIZONTAL WET VENT. CURRENTLY, THE SHOWER AND WATER
 CLOSET ARE BOTH UPSTREAM.
  
 6. SEVERAL PLACES THROUGHOUT THE WATER RISERS THE HW
 AND CW ARE MISLABLED AND CRISS CROSSED. CHECK FOR
 ACCURACY.
  
 7. P7.00 DETAIL #1 - OVERALL SANITARY RISER - PLEASE
 ADD THE VENT STACKS TO THE SANITARY RISER.
  
 8. P7.01 DETAIL #1 -- 2017 WPB AMENDS 107.3.5.1.3 - FOR
 CLARITY, WHERE DO THE CONDENSATE RISERS TERMINATE? THEY
 NEED TO BE VENTED AND VENTS NEED TO TERMINATE IN
 ACCORDANCE WITH 903,
  
 9. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE DETAIL THE
 STORM RISERS FOR ROOF DRAINAGE AND INCLUDE THE GPM FOR
 EACH RISER AND HORIZONTAL.
  
 10. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A DETAIL FOR THE
 SUMP PUMP FOR THE ELEVATOR SHAFTS THAT INCLUDES THE OIL
 ALARM OR INTERCEPTOR REQUIRED BY 1003.4.
  
 11. 2020 FPC 403.1.1 - FLOORS 1 APPEARS TO HAVE A
 REQUIREMENT FOR TWO BATHROOMS, 1 MALE AND 1 FEMALE.
 ONLY ONE IS PROVIDED. PER 403.2.1 - YOU COULD PROVIDE
 FAMILY OR ASSISTED-USE TOILET FACILITIES, BUT STILL ARE
 REQUIRED TO PROVIDE 2 BATHROOMS.
  
 12. 2020 FPC 403.1.1 - FLOOR 2 - THE OCCUPANT LOAD
 REQUIRES MORE WATER CLOSETS THAN THOSE PROVIDED.
  
 13. 2020 FPC 403.1.1 - FLOOR 3 - THE OCCUPANT LOAD
 TABLE HAS 2ND FLOOR IN THE COLUMN TO THE LEFT BUT IS
 FOR FLOOR 3. AND IT APPEARS THAT THE OCCUPANT LOAD
 NEEDS TO BE RECONFIGURED. IT DOES NOT APPEAR TO BE
 ACCURATE. PLEASE CHECK AND RECONFIGURE.
  
 14. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE INCLUDE THE
 HOT WATER PIPING DETAILS AND WHERE THE HOT WATER SOURCE
 WILL BE.
  
 15. PAGE A1.2.2 - POOL EQUIP. - 2017 WPB AMENDS
 107.3.5.1.3 - ALTHOUGH THE POOL WILL BE ON A SEPARATE
 PERMIT, PLEASE DETAIL A COMPLIANT DRAIN FOR THE
 DISCHARGE OF THE POOL EQUIPMENT.
 NOTE FOR POOL DISCHARGE:
 SEC 90 - 205 EXCEPTIONS TO DISCHARGING POOL WASTE INTO
 STORM WATER SYSTEM
  SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO
 SANITARY SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC
 UTILITIES DEPARTMENT.
  SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORM WATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
  - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
  - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
  - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
  - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
  - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
  - FOR STORM WATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 16. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND
 SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR
 PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE
 DEVICE SHOULD CONFORM TO ASSE 1070.
  
 17. 2017 WPB AMENDS 107.3.5.1.3 - INCLUDE IN THE
 FIXTURE SCHEDULE THE FIXTURES FOR THE RESIDENTIAL
 UNITS, WATER SUB-METERS, COMMON WATER HEATER, ETC.
  
 18. 2017 WPB AMENDS 107.3.5.1.3 - TYPICALLY THERE ARE
 EXTERIOR HOSE BIBS, IF APPLICABLE, ADD THESE TO THE
 PLAN.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  