2023-03-01 06:27:24 | 1ST REVIEW FMC |
| PERMIT: 23020018 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A KEY PLAN FOR THIS PROJECT INDICATING THE |
| LOCATION OF THE PROJECT TO INDICATE THE AIR INTAKES AND |
| EXHAUST TERMINATION LOCATIONS WILL MEET THE |
| REQUIREMENTS OF FMC 401 INTAKES AND FMC 501 EXHAUST |
| TERMINATION LOCATIONS. |
| |
| 2) ADD A NOTE ON THE MECHANICAL DRAWING STATING THAT |
| THE GENERATOR WILL REQUIRE A SEPARATE APPLICATION WITH |
| DOCUMENTS AND SEPARATE PLAN REVIEW AS THE GENERATOR |
| WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| |
| 3) SHOW THAT THE PARKING GARAGE WILL MEET THE |
| VENTILATION REQUIREMENTS OF FMC 404.1 AND PROVIDE THE |
| DRAWING SHOWING THE DESIGN. |
| |
| 4) SHOW THE GARAGE EXHAUST FANS MEET THE EXHAUST |
| DISCHARGE REQUIREMENTS OF 10 FEET FROM OPERABLE |
| OPENINGS. FMC 501.3 EXCEPTION 2. |
| |
| 5) SHEET M600: THE FOLLOWING OCCUPANCY CLASSIFICATIONS |
| SHOULD BE CALCULATED WITH THE OCCUPANT DENSITY FROM FMC |
| 403.3.1.1 AND NOT THE ARCHITECT???S EGRESS COUNT. |
| FITNESS, LOUNGE, CONFERENCE. ALSO SPECIFY THE FITNESS |
| ROOM, IS IT AEROBICS OR WEIGHTS? FMC 403.3.1.1 |
| |
| 6) THE OCCUPANT COUNT FOR THE BREAKROOM SHOULD ALSO BE |
| CALCULATED BY USING THE OCCUPANCY CLASSIFICATION THAT |
| MOST RESEMBLES THE USE OF SPACE AS DETERMINED IN FMC |
| TABLE 403.3.1.1. A BREAKROOM IS NORMALLY ASSOCIATED AS |
| A PLACE FOR EMPLOYEES TO USE DURING A BREAK FROM WORK, |
| AS TO RELAX, SOCIALIZE OR EAT. FMC 403.3.1.1 |
| |
| 7) SHEET M600: AHU-1 AND AHU-2 ARE SHOWN IN THE |
| MECHANICAL EQUIPMENT SIZING CALCULATIONS. AHU???S |
| 3A,3B,3C AND 3D ARE NOT INCLUDED IN THE MECHANICAL |
| EQUIPMENT SIZING CALCULATIONS. PROVIDE THESE AHU???S IN |
| THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. FEC |
| C403.2.1 |
| |
| 8) SHEET M1.00: EXPLAIN HOW THE GENERATOR ROOM WILL BE |
| PROVIDED WITH MAKE UP AIR FOR THE EXHAUSTED AIR. FMC |
| 501.4 |
| |
| 9) SHEET M1.00: EXPLAIN THE 48 X 22 DUCT THAT IS GOING |
| UP TO THE COURTYARD. WHAT IS THE USE OF THIS DUCTWORK? |
| FBC 107.3.5 |
| |
| 10) SHOW THE PENETRATION PROTECTION REQUIRED FOR THE 10 |
| X 10 O/A DUCT WORK AT THE FLOOR/CEILING OF FIRST FLOOR. |
| FMC 607 |
| |
| 11) SHEET M4.00: SHOW THE OUTDOOR AIR DUCTWORK FOR THE |
| AHU???S 3C AND 3D. FMC 403.3.1.1 |
| |
| 12) PROVIDE THE VENTILATION METHOD, NATURAL OR |
| MECHANICAL, FOR EACH UNIT. IF NATURAL SHOW THE |
| CALCULATIONS, IF MECHANICAL SHOW THE DUCTWORK FOR THE |
| OUTDOOR AIR. FMC 402 OR 403. |
| |
| 13) PROVIDE THE DRYER DUCT LENGTHS FOR THE UNIT DRYERS. |
| FMC 504.8.5 |
| |
| 14) SHOW THE CFM???S OF EXHAUST FOR THE DRYERS AND IF |
| NEEDED SHOW HOW THE MAKEUP AIR WILL BE BROUGHT INTO THE |
| DRYER CLOSET. FMC 504.6 |
| |
| 15) ADD A NOTE STATING THAT ALL ENVIRONMENTAL AIR WILL |
| TERMINATE A MINIMUM OF 3 FEET FROM ALL OPERABLE |
| OPENINGS INTO THE BUILDING. FMC 501.3 EXCEPTION 3 |
| |
| 16) SHOW THE RETURN AIR PATH FROM THE BEDROOMS OF THE |
| UNITS THAT HAVE A DOOR SEPARATING THE BEDROOM FROM THE |
| LIVING SPACE. FMC 601.6 |
| |
| 17) SHOW THE DOORS FOR THE AHU CLOSETS WILL MEET THE |
| RETURN AIR AND THE MATERIAL OF THE DOORS WILL MEET FMC |
| 602.2.1 MATERIALS IN PLENUMS. |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |