2023-02-13 12:25:08ELECTRIC REVIEW FAILED
  
 1) THERE ARE MANY CONFLICTS WITH PANEL SCHEDULE
 DESCRIPTION TITLE BLOCKS. EXAMPLES ARE, SCHEDULES
 INCORRECTLY DETAILING, MLO, MB, BUS SIZE. IN ADDITION,
 MANY SCHEDULES OR RISER DETAIL INCORRECT SUB PANEL
 BREAKER SIZES WHICH ARE IN CONFLICT WITH RISER DIAGRAM.
 PLEASE PROVIDE CORRECTIONS TO ALL PANEL SCHEDULES AND
 RISER AS APPLICABLE.
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING
 JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE
 PROVIDED
 PRIOR TO THE INSTALLATION OF THE FEEDERS.
  
 2) PLEASE DETAIL CONDUCTOR, AND CORRECT OVERCURRENT
 PROTECTION SIZE FOR PANEL OPG BOTH ON RISER AND PANEL
 SCHEDULE. FBC 107.2 AND NEC 215.5
  
 3) PLEASE DETAIL OVERCURRENT PROTECTION TO PANEL OP5
 FROM MPD-1 ON RISER DIAGRAM. FBC 107.2 AND NEC 215.5
  
 4) PLEASE DETAIL GENERATOR CONTROL CONDUIT TO FIRE PUMP
 CONTROLLER, EITHER BY NOTE OR PLANS TO BE INSTALLED AS
 PER NEC 695.14 GENERATOR CONTROL WIRING METHODS,
 INTEGRITY AND FIRE RATING
  
 5) PLEASE DETAIL IN RISER DIAGRAM COMPLIANCE WITH
 EMERGENCY SYSTEMS, NEC 700.3 (F) TEMPORARY SOURCE OF
 POWER FOR MAINTENANCE OR REPAIR OF THE ALTERNATE SOURCE
 OF POWER.
  
 6) PLEASE DETAIL GENERATOR SUPPLIED NATURAL GAS TO BE
 SUPPLIED BY ALTERNATE FUEL SOURCE AS REQUIRED PER NEC
 700.12 (B)(3) DUAL SUPPLIES. PRIME MOVERS SHALL NOT BE
 SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR
 THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR
 COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED.
  
 7) PLEASE DETAIL ALL PANIC HARDWARE FOR MAIN ELECTRIC
 ROOM DOORS AS REQUIRED OF NEC 110.26(C)(3)
  
 8) PLEASE PROVIDE BY NOTE COMPLIANCE WITH NEC 408.4(B)
 FIELD IDENTIFICATION REQUIRED FOR SOURCE OF SUPPLY FOR
 SWITCH AND PANEL BOARDS
  
 9) PLEASE PROVIDE AN ENTIRE BUILDING ELECTRIC LOAD
 CALCULATION.
  
 NEC 215.5 AND NEC 215.2 FEEDER CONDUCTORS SHALL HAVE AN
 AMPACITY NOT LESS THAN REQUIRED TO SUPPLY THE LOAD
  
 10) PLEASE PROVIDE INFORMATION ON THE USE OF GROUND
 FLOOR ROOM 102 LABELED METER ROOM. FBC 107.2
  
 11) PLEASE CALL OUT ALL GROUNDING ELECTRODE CONDUCTOR
 SIZES, NOT CODE ARTICLES, AS REQUIRED BY NEC 250.66
  
 12) MANY APARTMENT PANEL SCHEDULES ARE MISSING ELECTRIC
 LOADS, IE WATER HEATERS AND AIR CONDITIONING. FBC 107.2
  
 13) PLEASE DETAIL ALL RECEPTACLES IN COMMON AREAS, AS
 APPLICABLE AND REQUIRED BY NEC 210.8 (B)(2)(KITCHENS)
 AS GFI PROTECTED
  
 14) MANY CIRCUITS IN APARTMENT PANEL SCHEDULES ARE NOT
 DETAILED AS ARC FAULT PROTECTED, AS REQUIRED BY NEC.
 210.13 PLEASE CORRECT AS APPLICABLE
  
 15) PLEASE CORRECT LABELING ON SHEET E-400, OF ROOM
 DETAILED AS DOMESTIC AN FIRE PUMP ROOM AS APPLICABLE.
 FBC 107.2
  
 16) PLEASE PROVIDE A NOTE STATING, LIGHTNING
 PROTECTION, VOICE, DATA, SECURITY, AUDIO, VIDEO, FIRE
 ALARM, ACCESS CONTROL, ENERGY MANAGEMENT, GENERATOR,
 SIGN, SITE LIGHTING, POOL AND BDA WIRING REQUIRE
 SEPARATE PERMITS
  
 17) PLEASE DETAIL ALL SMOKE/CARBON ALARMS IN ALL UNITS
 AS REQUIRED BY FBC R314 AND R315
  
 18) PLEASE DETAIL FAN TEF ON ROOF POWER PLAN. FBC 107.2
  
 19) PLEASE DETAIL (2) ELEVATOR CONTROLLER ON ROOF POWER
 PLAN. FBC 107.2
  
 20) PLEASE DETAIL GFI PROTECTION OF APPROPRIATE LOADS
 IN PANEL OF, IE DRINKING FOUNTAIN, KITCHEN AREAS
  
 21) PLEASE DETAIL ROOF LIGHTS ON ROOF POWER PLAN. FBC
 107.2
  
 22) PLEASE PROVIDE ALL ELECTRIC ROOM DETAILS AS ALL ARE
 NOT THE SAME. PLEASE INCLUDE ALL EQUIPMENT AND
 DIMENSIONS TO ENSURE COMPLIANCE WITH WORKING CLEARANCES
 AS REQUIRED BY NEC 110.26
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER