2023-02-13 12:25:08 | ELECTRIC REVIEW FAILED |
| |
| 1) THERE ARE MANY CONFLICTS WITH PANEL SCHEDULE |
| DESCRIPTION TITLE BLOCKS. EXAMPLES ARE, SCHEDULES |
| INCORRECTLY DETAILING, MLO, MB, BUS SIZE. IN ADDITION, |
| MANY SCHEDULES OR RISER DETAIL INCORRECT SUB PANEL |
| BREAKER SIZES WHICH ARE IN CONFLICT WITH RISER DIAGRAM. |
| PLEASE PROVIDE CORRECTIONS TO ALL PANEL SCHEDULES AND |
| RISER AS APPLICABLE. |
| |
| FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| AUTHORITY HAVING |
| JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE |
| PROVIDED |
| PRIOR TO THE INSTALLATION OF THE FEEDERS. |
| |
| 2) PLEASE DETAIL CONDUCTOR, AND CORRECT OVERCURRENT |
| PROTECTION SIZE FOR PANEL OPG BOTH ON RISER AND PANEL |
| SCHEDULE. FBC 107.2 AND NEC 215.5 |
| |
| 3) PLEASE DETAIL OVERCURRENT PROTECTION TO PANEL OP5 |
| FROM MPD-1 ON RISER DIAGRAM. FBC 107.2 AND NEC 215.5 |
| |
| 4) PLEASE DETAIL GENERATOR CONTROL CONDUIT TO FIRE PUMP |
| CONTROLLER, EITHER BY NOTE OR PLANS TO BE INSTALLED AS |
| PER NEC 695.14 GENERATOR CONTROL WIRING METHODS, |
| INTEGRITY AND FIRE RATING |
| |
| 5) PLEASE DETAIL IN RISER DIAGRAM COMPLIANCE WITH |
| EMERGENCY SYSTEMS, NEC 700.3 (F) TEMPORARY SOURCE OF |
| POWER FOR MAINTENANCE OR REPAIR OF THE ALTERNATE SOURCE |
| OF POWER. |
| |
| 6) PLEASE DETAIL GENERATOR SUPPLIED NATURAL GAS TO BE |
| SUPPLIED BY ALTERNATE FUEL SOURCE AS REQUIRED PER NEC |
| 700.12 (B)(3) DUAL SUPPLIES. PRIME MOVERS SHALL NOT BE |
| SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR |
| THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR |
| COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR |
| AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO |
| ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED. |
| |
| 7) PLEASE DETAIL ALL PANIC HARDWARE FOR MAIN ELECTRIC |
| ROOM DOORS AS REQUIRED OF NEC 110.26(C)(3) |
| |
| 8) PLEASE PROVIDE BY NOTE COMPLIANCE WITH NEC 408.4(B) |
| FIELD IDENTIFICATION REQUIRED FOR SOURCE OF SUPPLY FOR |
| SWITCH AND PANEL BOARDS |
| |
| 9) PLEASE PROVIDE AN ENTIRE BUILDING ELECTRIC LOAD |
| CALCULATION. |
| |
| NEC 215.5 AND NEC 215.2 FEEDER CONDUCTORS SHALL HAVE AN |
| AMPACITY NOT LESS THAN REQUIRED TO SUPPLY THE LOAD |
| |
| 10) PLEASE PROVIDE INFORMATION ON THE USE OF GROUND |
| FLOOR ROOM 102 LABELED METER ROOM. FBC 107.2 |
| |
| 11) PLEASE CALL OUT ALL GROUNDING ELECTRODE CONDUCTOR |
| SIZES, NOT CODE ARTICLES, AS REQUIRED BY NEC 250.66 |
| |
| 12) MANY APARTMENT PANEL SCHEDULES ARE MISSING ELECTRIC |
| LOADS, IE WATER HEATERS AND AIR CONDITIONING. FBC 107.2 |
| |
| 13) PLEASE DETAIL ALL RECEPTACLES IN COMMON AREAS, AS |
| APPLICABLE AND REQUIRED BY NEC 210.8 (B)(2)(KITCHENS) |
| AS GFI PROTECTED |
| |
| 14) MANY CIRCUITS IN APARTMENT PANEL SCHEDULES ARE NOT |
| DETAILED AS ARC FAULT PROTECTED, AS REQUIRED BY NEC. |
| 210.13 PLEASE CORRECT AS APPLICABLE |
| |
| 15) PLEASE CORRECT LABELING ON SHEET E-400, OF ROOM |
| DETAILED AS DOMESTIC AN FIRE PUMP ROOM AS APPLICABLE. |
| FBC 107.2 |
| |
| 16) PLEASE PROVIDE A NOTE STATING, LIGHTNING |
| PROTECTION, VOICE, DATA, SECURITY, AUDIO, VIDEO, FIRE |
| ALARM, ACCESS CONTROL, ENERGY MANAGEMENT, GENERATOR, |
| SIGN, SITE LIGHTING, POOL AND BDA WIRING REQUIRE |
| SEPARATE PERMITS |
| |
| 17) PLEASE DETAIL ALL SMOKE/CARBON ALARMS IN ALL UNITS |
| AS REQUIRED BY FBC R314 AND R315 |
| |
| 18) PLEASE DETAIL FAN TEF ON ROOF POWER PLAN. FBC 107.2 |
| |
| 19) PLEASE DETAIL (2) ELEVATOR CONTROLLER ON ROOF POWER |
| PLAN. FBC 107.2 |
| |
| 20) PLEASE DETAIL GFI PROTECTION OF APPROPRIATE LOADS |
| IN PANEL OF, IE DRINKING FOUNTAIN, KITCHEN AREAS |
| |
| 21) PLEASE DETAIL ROOF LIGHTS ON ROOF POWER PLAN. FBC |
| 107.2 |
| |
| 22) PLEASE PROVIDE ALL ELECTRIC ROOM DETAILS AS ALL ARE |
| NOT THE SAME. PLEASE INCLUDE ALL EQUIPMENT AND |
| DIMENSIONS TO ENSURE COMPLIANCE WITH WORKING CLEARANCES |
| AS REQUIRED BY NEC 110.26 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |