2023-03-27 11:27:14 | PLAN REVIEW COMMENTS |
| |
| 23020018 |
| 512 CLEMATIS STREET |
| 5 STORY |
| III-B CONSTRUCTION TYPE |
| 88 APARTMENTS |
| MIXED USE |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT A SIGNED AND SEALED GEOTECHNICAL SOILS REPORT |
| IN ACCORDANCE WITH FBC 1801.2. |
| |
| 2) THIS PROJECT IS A THRESHOLD BUILDING. THRESHOLD |
| BUILDING / FL S. S. 553.71(7) "THRESHOLD BUILDING" |
| MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES |
| OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| |
| A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| |
| C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| |
| D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. |
| |
| F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE. |
| |
| G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| CEILINGS. |
| |
| J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER |
| 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS IF |
| YOU NEED IT. |
| |
| 3) SUBMIT A MANAGEMENT OF TRAFFIC (MOT) PLAN, INCLUDING |
| PROTECTION OF PEDESTRIANS. FBC 3301 |
| |
| 4) SHOW HOW THE ADJOINING PROPERTIES WILL BE PROTECTED |
| FROM DAMAGE DURING CONSTRUCTION PER FBC 3307. |
| |
| 5) ON SHEET SP-1, THERE ARE SOME ERRORS. UNDER |
| APPLICABLE CODES THE FBC EXISTING BUILDING IS LISTED |
| AND THIS IS NEW CONSTRUCTION. PLEASE REMOVE. FBC |
| 107.2.1 |
| |
| 6) ON SHEET SP-1, THE CONSTRUCTION TYPE IS SPECIFIED AS |
| IB. IT IS SPECIFIED AS TYPE IIIB ON THE OTHER SHEETS. |
| PLEASE CORRECT. FBC 602.1 |
| |
| 7) ON SHEET ALS.0.1, THE FIRE RESISTANCE RATING IN |
| TABLE 602 FOR 10' TO LESS THAN 30' FOR 3B CONSTRUCTION |
| SHOULD BE 1 HOUR PER FBC TABLE 602. |
| |
| 8) THE PRODUCT APPROVALS FOR THE ROOFING MATERIALS IS |
| NOT SPECIFED IN THE LIST OF DEFERRED SUBMITTALS ON |
| SHEET ALS.0.1. FBC 107.3.4 |
| |
| 9) ON SHEET ALS.1.1, THE GROUND FLOOR LIFE SAFETY PLAN |
| HAS EXIT CORRIDORS 100 AND 103. THESE ARE EXIT |
| PASSAGEWAYS PER THE DEFINITION IN CHAPTER 2 OF THE FBC |
| AND ARE CONSIDERED EXTENSIONS OF THE EXIT STAIRWAYS. |
| PLEASE LABEL THEM ACCORDINGLY AND ENSURE THAT THEY |
| COMPLY WITH FBC SECTION 1024. |
| |
| 10) PLEASE CLARIFY IF THE PARKING SPACES PROVIDED IN |
| THE ENCLOSED PARKING GARAGE ARE FOR THE APARTMENTS OR |
| THE BUSINESS AND MERCANTILE OCCUPANCIES. FBC 107.2.1 |
| |
| 11) THERE IS ONE REQUIRED ACCESSIBLE PARKING SPACE |
| PROVIDED IN THE ENCLOSED PARKING GARAGE PER FBC |
| ACCESSIBILITY TABLE 208.2. FBC ACCESSIBILITY 208.2.4 |
| REQUIRES AT LEAST ONE VAN ACCESSIBLE PARKING SPACE FOR |
| EVERY SIX OR FRACTION OF SIX PARKING SPACES REQUIRED BY |
| 208.2 THAT COMPLIES WITH 502. SHOW THAT THE ONE |
| ACCESSIBLE SPACE COMPLIES WITH FBC ACCESSIBILITY 502. |
| |
| 12) SHOW ON THE PLANS THAT A VERTICAL CLEARANCE OF 98" |
| (8' 2") WILL BE PROVIDED FOR THE VAN PARKING SPACE AND |
| ACCESS ISLE AND THE VEHICULAR ROUTE SERVING IT. FBC |
| ACCESSIBILITY 502.5 |
| |
| 13) ON SHEET ALS.4.1, THE UNIT IN THE SOUTH EAST CORNER |
| IS LABELED KITCHEN. PLEASE CORRECT. FBC 107.2.1 |
| |
| 14) ON SHEET ALS.4.1, LIFE SAFETY PLAN IS LABELED FIFTH |
| FLOOR. IT SHOULD BE LABELED FOURTH AND FIFTH FLOOR. FBC |
| 107.2.1 |
| |
| 15) ON SHEET ALS.4.1, THE THREE UNITS IN THE NORTHEAST |
| CORNER HAVE ONLY ONE MEANS OF EGRESS AND MUST PASS BY |
| THE ELEVATORS TO GET TO THE EXIT STAIRWAY. FBC 1006 |
| |
| 16) SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO |
| ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING THAT IS |
| MORE THAN THREE STORIES HIGH OR IN WHICH THE VERTICAL |
| DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING AND THE |
| TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE |
| CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR |
| THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE |
| DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR |
| CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO |
| ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76 |
| INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH |
| (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN |
| POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL |
| SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). |
| THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN |
| HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE |
| HOISTWAY DOOR FRAME. |
| |
| 17) SHOW HOW THE SPA POOL WILL COMPLY WITH FBC |
| ACCESSIBILITY SECTION 242.2 SWIMMING POOLS. AT LEAST |
| TWO ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED FOR |
| SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY SHALL BE |
| SWIMMING POOL LIFTS COMPLYING WITH 1009.2; SLOPED |
| ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS COMPLYING |
| WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH 1009.5; |
| AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST ONE |
| ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY WITH |
| 1009.2 OR 1009.3. |
| EXCEPTIONS: |
| 1. WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET |
| (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED |
| THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL |
| LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING |
| WITH 1009.3. |
| 2. WAVE ACTION POOLS, LEISURE RIVERS, SAND BOTTOM |
| POOLS, AND OTHER POOLS WHERE USER ACCESS IS LIMITED TO |
| ONE AREA SHALL NOT BE REQUIRED TO PROVIDE MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE ACCESSIBLE |
| MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH |
| 1009.2, A SLOPED ENTRY COMPLYING WITH 1009.3, OR A |
| TRANSFER SYSTEM COMPLYING WITH 1009.5. |
| 3. CATCH POOLS SHALL NOT BE REQUIRED TO PROVIDE AN |
| ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE CATCH POOL |
| EDGE IS ON AN ACCESSIBLE ROUTE. |
| |
| COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE |
| RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL |
| FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO |
| THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT |
| COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, |
| INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. |
| IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY |
| IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS |
| REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON |
| THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER |
| STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. |
| |
| 18) SUBMIT A DETAILED COST BREAKDOWN FOR THIS PROJECT. |
| THIS WILL PREVENT US FROM CHARGING YOU DOUBLE FOR ITEMS |
| THAT REQUIRE SEPARATE PERMITS. BUILDING PERMIT |
| VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC |
| 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 19) A. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| |
| COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| PRESSURES SHOWN ON SHEET S0.0.5) |
| |
| COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| COMPLY WITH MINIMUM DESIGN PRESSURES. |
| |
| B. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| REQUIRED FOR: |
| LIGHT POLES/SITE LIGHTING |
| FIRE ALARM |
| FIRE SPRINKLER |
| LOW VOLTAGE |
| ACCESS |
| LANDSCAPING |
| IRRIGATION |
| PARKING LOT |
| SWIMMING POOLS AND SPAS |
| GENERATORS |
| ALL OTHER ITEMS OTHER THAN BMEP |
| |
| C. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| PRIOR TO C.O. |
| |
| D. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE |
| SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE |
| ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED |
| PRIOR TO CONCRETE POUR. |
| |
| E. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS |
| REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. |
| |
| F. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| |
| 20) THE WEST ELEVATION ON SHEET A3.0.2 APPEARS TO SHOW |
| WINDOWS WHERE OPENINGS ARE NOT PERMITTED PER FBC |
| 705.8.1. PLEASE CLARIFY. |
| |
| 21) SHOW THE CALCULATIONS FOR THE ALLOWABLE AREA OF |
| OPENINGS FOR EACH STORY OF THE SOUTH ELEVATION AS |
| REQUIRED BY FBC 705.8.1. SHOW THE DISTANCE FROM THE |
| WEST WALL TO THE CENTER OF THE ALLY ON THE PLANS. |
| |
| 22) PROVIDE A FLOOR AREA BREAKDOWN BY OCCUPANCY TYPE |
| FOR EACH FLOOR OF THE PROPOSED BUILDING. FBC 107.2.1 & |
| 503.1 |
| |
| 23) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. THE |
| RESPONSES TO THESE COMMENTS MAY RESULT IN ADDITIONAL |
| COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |