2023-02-08 07:36:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE LOAD CALCULATION FO EXISITNG SERVICE PLUS |
| ANY NEW LOADS FROM POOL PANEL/EQUIPMENT FBC 107.2.1 NEC |
| 220 |
| |
| 2. PROVIDE CUT SHEETS FOR NEW PUMP FOR PRODUCT |
| APPROVAL. FBC 107.2.1 NEC 110.2 110.3B |
| |
| 3. HOW CAN THERE BE ZERO CHANGE IN VALUE WITH A |
| REVISION SHOWING NEW ADDITIONAL WORK? PROVIDE ACCURATE |
| COST BREAKDOWN ON REVISION FORM FOR NEW PROPSOED WORK. |
| FBC 109.3 |
| |
| END OF COMMENTS. |
| |