Plan Review Notes
Plan Review Notes For Permit 23020002
Permit Number 23020002
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-08 07:36:04ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FO EXISITNG SERVICE PLUS
 ANY NEW LOADS FROM POOL PANEL/EQUIPMENT FBC 107.2.1 NEC
 220
  
 2. PROVIDE CUT SHEETS FOR NEW PUMP FOR PRODUCT
 APPROVAL. FBC 107.2.1 NEC 110.2 110.3B
  
 3. HOW CAN THERE BE ZERO CHANGE IN VALUE WITH A
 REVISION SHOWING NEW ADDITIONAL WORK? PROVIDE ACCURATE
 COST BREAKDOWN ON REVISION FORM FOR NEW PROPSOED WORK.
 FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  