Plan Review Notes
Plan Review Notes For Permit 23011480
Permit Number 23011480
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-02-03 12:02:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE REAR EXITS INDICATED ON THE LIFE SAFETY
 PLANS,
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 THERE MAY BE A SERVICE ROAD NEXT TO THE RR, HOWEVER, I
 BELIEVE A FENCE IS BEING PROPOSED THAT MAY
 LIMIT/RESTRICT PASSAGE IN EITHER DIRECTION.
  
 THERE MAY ALSO BE GATES ALONG THIS FENCE THAT NEEDS TO
 BE ACCESSIBLE.
  
 AN ADDITIONAL CONCERN IS THAT THERE MAY BE UNPROTECTED
 OPENINGS ALONG ALL THE VARIOUS OCCUPANCIES ALONG THE
 FENCE LINE THAT COULD EXPOSE PEDESTRIANS TO THE EFFECTS
 OF FIRE AND SMOKE.
  
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE REQUIRED
 CODE.
  
  
  
 2) THERE ARE INDICATIONS WITHIN THE DOOR SCHEDULE THAT
 DO NOT APPEAR TO MEET THE NFPA 101 CH 7, MEANS OF
 EGRESS & CH 12 NEW ASSEMBLY REQUIREMENTS FOR ASSEMBLY
 OCCUPANCIES.
  
 7.2.1.7* PANIC HARDWARE AND FIRE EXIT HARDWARE.
  
 7.2.1.7.1 WHERE A SIDE-HINGED OR PIVOTED-SWINGING DOOR
 ASSEMBLY IS
 REQUIRED TO BE EQUIPPED WITH PANIC OR FIRE EXIT
 HARDWARE, SUCH HARDWARE
 SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, WITH
 THE LENGTH OF THE
 ACTUATING PORTION OF THE CROSS BAR OR PUSH PAD NOT LESS
 THAN ONE-HALF
 OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND
 NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF
 (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND LATCHES
  
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAP TERS 22 AND 23, SHALL NOT BE EQUIPPED
 WITH ANY LOCKING DEVICE, SET SCREW,
 OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE OF THE
 LATCH WHEN PRESSURE
 IS APPLIED TO THE RELEASING DEVICE
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE. DELINEATE
  
  
 PETER LEDUC
 FIRE MARSHAL