2023-03-28 11:02:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 23011451 |
| ADD: 1805 N FLAGLER DR # 219 |
| CONT: PM BUILDERS |
| TEL: 561-425-8525 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. MARCH 28TH/2023 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE SHEET A1 DEMO PLAN NOTE # 7 STATES |
| REMOVE EXISTING FLOORING AS SHOWN. SHEETA2 THE PROPOSED |
| FLOOR PLAN. NOTE ON THE PLAN STATES NEW FLOOR MATERIAL |
| PICKED BY OWNER. CONTRACTOR LETTER PROVIDES PORCELAIN |
| PLANK TILE, BUT NOT REVIEWED BY THE DESIGNER OF RECORD |
| FOR AREVIEW. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. |
| 3-22-2023 SUBMITTED TEST REPORT FOR PROFLEX MSC 90 8.0 |
| INCH SLAB, NO DROPPED CEILING. 1801-1805 N. FLAGLER DR. |
| HAVE 7 INCH SLABS ( PERMIT 99040411) NOT 8 INCH SLABS, |
| PROFLEX MSC 90 HAS NO TEST FOR 6 INCH SLABS , NOR FLAME |
| SPREAD. |
| |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1A) 2ND REVIEW. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) 2N REVIEW. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) 2ND REVIEW. FLAME SPREAD- FBC-B 2020 603.1. |
| EXCEPTION 2. (TILE & MARBLE) INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| OR |
| 1C) 2ND REVIEW. FBC-B 804.4.4.1 SOFT FLOOR FINISHES |
| (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING) |
| WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 |
| ???PILL TEST??? (CPSC 16 CFR PART 1630) OR WITH ASTM |
| D2859. |
| LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253. |
| |
| 2) NEW COMMENT. SHEET A-2 TYPICAL DROPPED SOFFIT HAS |
| NOT PROVIDED THE TYPE OF ANCHOR AND SPACING OF ANCHOR |
| OR DEPTH OF ANCHOR TO THE CONCRETE DECK ABOVE THIS A |
| GENERIC DETAIL AND STATES THE CONTRACTOR IS TO INSTALL |
| METAL FRAMING AS PER GYPSUM CONSTRUCTION HANDBOOK THE |
| DESIGN PROFESSIONAL HAS TO TAKE OWNERSHIP, THIS MAY |
| ALSO BE OUT OF THE INTERIOR DESIGNER LICENSE SCOPE. FS |
| 481.2131. |
| THE SAME HOLDS TRUE FOR PIPES THAT PENETRATE FIRE RATED |
| WALLS (2020 FBC-BUILDING 714.3) AND PENETRATIONS, FIRE |
| RESISTANCE RATED ASSEMBLIES, (FBC-BUILD. 714.3.1.1). |
| MEMBRANE PENETRATIONS (2020 FBC-BUILD. 714.3.2). |
| A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |