2023-02-20 09:08:42FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION (FEEDER INFORMATION - WIRES AND
 PROTECTION) OF THE NEW ACCU 1 AND NEW ACCU 2 ON THE
 REPLACE PANEL A SCHEDULE. NEC 408.4(A).
  
 2. PROVIDE THE EGC FOR REPACE PANEL A IN ACCORDANCE
 WITH NEC TABLE 250.122.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  