Plan Review Notes For Permit 23011421 |
Permit Number |
23011421 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-20 09:08:42 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE INFORMATION (FEEDER INFORMATION - WIRES AND | | PROTECTION) OF THE NEW ACCU 1 AND NEW ACCU 2 ON THE | | REPLACE PANEL A SCHEDULE. NEC 408.4(A). | | | | 2. PROVIDE THE EGC FOR REPACE PANEL A IN ACCORDANCE | | WITH NEC TABLE 250.122. | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|