Plan Review Notes For Permit 23011403 |
Permit Number |
23011403 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-07 14:26:24 | ELECTRIC REVIEW FAILED | | | | 1) PLEASE PROVIDE ANY ELECTRICAL WORK PLANS FOR NEW | | GATE AS APPLICABLE. IF GATES ARE NOT MOTORIZED AND | | THERE IS NO ELECTRIC WORK REQUIRED , PLEASE STATE NO | | ELECTRIC WORK IS TO BE DONE ON SUBMITTED PLANS. FBC | | 107.2 | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | |
|